Skip to main content
Siemens 3VA2110-6HN32-0KC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-6HN32-0KC0 SENTRON MCCB, 100A, 242kA at 240V

MPN3VA2110-6HN32-0KC0

Siemens SENTRON 3VA2110-6HN32-0KC0, molded case circuit breaker, 3-pole, 100 A, ETU350, line protection, 242 kA at 240 V, shunt trip, 2 auxiliary switches HQ.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2110-6HN32-0KC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2110-6HN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2110-6HN32-0KC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96.25 A
Current at 60 °C92.5 A
Current at 65 °C88.75 A
Current at 70 °C85 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V5 kA
Power loss, max.10 W

Protection & Trip Unit

3VA2110-6HN32-0KC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350

Construction & Connection

3VA2110-6HN32-0KC0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2110-6HN32-0KC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2110-6HN32-0KC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2110-6HN32-0KC0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

What this MCCB is and what it does

The Siemens 3VA2110-6HN32-0KC0 is a SENTRON molded case circuit breaker (MCCB) rated for 100 A continuous current at 40 °C, with a rated insulation voltage of 800 V. It's a 3-pole line-protection device fitted with an ETU350 electronic trip unit — that's the microprocessor-based release that gives you adjustable long-time, short-time, and instantaneous protection curves, plus ground-fault alarm capability if you ever add the module. The interrupting ratings are serious: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and still 5 kA at 690 V. That means it handles high-fault-current scenarios without cascading upstream — useful when you're feeding a panel off a large transformer or a utility service with stiff source impedance.

Built-in shunt trip and auxiliary contacts

This variant ships with a shunt trip (STL) release integrated — part number 3VA9688-0BL33 for the trip coil itself — and two auxiliary switches (HQ configuration) already wired in. The shunt trip lets you remotely trip the breaker from a PLC output, E-stop circuit, or fire-alarm panel. The two auxiliary switches give you status feedback (open/closed) without needing an add-on block. No undervoltage release, no communication module, no phase-failure detection on this build — it's a straightforward remote-trip + status package for a distribution panel or motor control center.

Thermal derating and panel fit

The breaker holds its full 100 A rating up to 50 °C ambient. Above that it derates linearly: 96.25 A at 55 °C, 92.5 A at 60 °C, 88.75 A at 65 °C, and 85 A at 70 °C — the maximum operating temperature. If your panel runs hot (say, a non-ventilated enclosure near a furnace line), you'll need to account for that derating in your load schedule. Physical dimensions are 181 mm high, 105 mm wide, 86 mm deep — standard SENTRON 3VA2 footprint, so it drops into the same mounting base and bus-bar system as other 3VA2 frame sizes. Power loss at rated current is 10 W max, which is modest for a 100 A MCCB; helps keep internal panel temperature down.

Frequently asked questions

What is the interrupting capacity of this MCCB at 240 V?

242 kA at 240 V, which covers high-fault scenarios like utility-service or large-transformer feeds.

What trip unit does this breaker use?

It uses an ETU350 electronic trip unit — microprocessor-based with adjustable long-time, short-time, and instantaneous protection.

Does this MCCB include a shunt trip?

Yes, it has a factory-integrated shunt trip (STL) release for remote tripping from a PLC or E-stop circuit.

What are the physical dimensions of 3VA2110-6HN32-0KC0?

181 mm high, 105 mm wide, 86 mm deep — standard 3VA2 frame footprint.

Where can I buy 3VA2110-6HN32-0KC0 and get current pricing?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

MPN
3VA2110-6HN32-0KC0