Skip to main content
Siemens 3VA2110-6HN36-0CH0 — Molded Case Circuit Breakers (MCCB)

SENTRON 3VA2110-6HN36-0CH0 MCCB, 100 A, 3-Pole, 242 kA at 24

MPN3VA2110-6HN36-0CH0

SENTRON 3VA2110-6HN36-0CH0 molded case circuit breaker, 100 A continuous, 3-pole, 242 kA SCCR at 240 V, undervoltage release, 2 auxiliary switches + 1 trip alarm.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2110-6HN36-0CH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21106HN360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA2110-6HN36-0CH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.12.5 W

Protection & Trip Unit

3VA2110-6HN36-0CH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2110-6HN36-0CH0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2110-6HN36-0CH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA2110-6HN36-0CH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2110-6HN36-0CH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The SENTRON 3VA2110-6HN36-0CH0 is a 3-pole molded case circuit breaker rated for 100 A continuous current across the full ambient range of 40 °C to 70 °C — no derating needed up to that ceiling. Its interrupting capacity hits 242 kA at 240 V, dropping to 187 kA at 415/440 V, 121 kA at 500 V, and 3.7 kA at 690 V. That SCCR headroom covers most industrial fault scenarios without cascading upstream. Line protection design, so it's the primary overcurrent device on a feeder or branch — not a motor-protector or ground-fault variant. Undervoltage release (UVR) built in, with two auxiliary switches plus a separate trip alarm switch (HQ type). No communication function, no ground-fault monitoring.

Sizing and coordination

At 100 A flat from 40 °C to 70 °C, the thermal-magnetic curve stays predictable — no surprise trip in a warm panel. The 242 kA SCCR at 240 V lets you coordinate downstream breakers without worrying about series rating limits; at 690 V the 3.7 kA figure is still enough for most 690 V distribution. Panel depth needed: 86 mm, width 105 mm, height 181 mm. Mounts on a standard DIN rail or panel-mount via the screw kit.

Frequently asked questions

Where can I buy 3VA2110-6HN36-0CH0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing.

What is the SCCR of 3VA2110-6HN36-0CH0 at 240 V?

242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3.7 kA at 690 V.

MPN
3VA2110-6HN36-0CH0