Skip to main content
Siemens 3VA2110-6HN36-0HA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-6HN36-0HA0 SENTRON MCCB, 100 A, 242 kA at 24

MPN3VA2110-6HN36-0HA0

Siemens SENTRON 3VA2110-6HN36-0HA0, molded case circuit breaker, 3-pole, 100 A rated continuous current, interrupting capacity 242 kA at 240 V, ETU350 release, shunt trip, line protection.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2110-6HN36-0HA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2110-6HN36-0AA0

Ratings

3VA2110-6HN36-0HA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96.25 A
Current at 60 °C92.5 A
Current at 65 °C88.75 A
Current at 70 °C85 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V5 kA
Power loss, max.10 W

Protection & Trip Unit

3VA2110-6HN36-0HA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350

Construction & Connection

3VA2110-6HN36-0HA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2110-6HN36-0HA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2110-6HN36-0HA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2110-6HN36-0HA0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

MCCB with 100 A continuous rating and 242 kA interrupting capacity

The Siemens SENTRON 3VA2110-6HN36-0HA0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current at 40 °C, with a maximum interrupting capacity of 242 kA at 240 V. The interrupting rating drops to 187 kA at 415 V and 440 V, 121 kA at 500 V, and 5 kA at 690 V — the 690 V figure is the low end of the curve, so confirm the available fault current at your system voltage. The ETU350 electronic trip unit provides adjustable overload and short-circuit protection; the shunt trip (STL) allows remote tripping via a separate control signal. Latching endurance is rated at 20 000 operations.

Thermal derating and panel fit

The 100 A rating holds flat from 40 °C through 50 °C; above that it derates linearly to 85 A at 70 °C. If the panel ambient runs above 50 °C, the continuous current must be reduced per the published curve. The enclosure dimensions are 105 mm wide, 181 mm high, and 86 mm deep — a standard 3-pole MCCB footprint for DIN-rail or screw-mount installation. Maximum power loss is 10 W.

Frequently asked questions

Where can I buy 3VA2110-6HN36-0HA0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the key interrupting ratings for this MCCB?

The interrupting capacity is 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 5 kA at 690 V.

What is the continuous current rating and how does it derate with temperature?

The rated continuous current is 100 A from 40 °C to 50 °C, then derates to 96.25 A at 55 °C, 92.5 A at 60 °C, 88.75 A at 65 °C, and 85 A at 70 °C.

What are the physical dimensions of this MCCB?

The enclosure measures 105 mm wide, 181 mm high, and 86 mm deep.

MPN
3VA2110-6HN36-0HA0