Skip to main content
Siemens 3VA2110-6JP36-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-6JP36-0AA0 SENTRON MCCB, 100 A, 3-Pole, 242

MPN3VA2110-6JP36-0AA0
Active

Siemens SENTRON 3VA2110-6JP36-0AA0, molded case circuit breaker, 3-pole, 100 A, interrupting rating 242 kA at 240 V, ETU550 electronic trip unit, IP40 front, communication function.

$461.01Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2110-6JP36-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2110-6JP36-0AA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.10 W
3VA2110-6JP36-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
Overcurrent protection functionLSI
Ground-fault monitoringWithout
3VA2110-6JP36-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2110-6JP36-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2110-6JP36-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2110-6JP36-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

Line protection MCCB with ETU550 — 100 A continuous, 242 kA interrupting at 240 V

Interrupting capacity reaches 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3.7 kA at 690 V — the steep drop above 500 V is the limiting factor for 690 V line-side applications; verify the fault current at your system voltage against these numbers. The breaker includes a communication function for remote monitoring and trip-event logging.

Footprint is 105 mm wide by 181 mm tall by 86 mm deep — a standard 3-pole MCCB envelope that drops into most SENTRON 3VA switchboard or distribution panel cutouts without re-drilling. Front protection is IP40, so the breaker is suited for indoor panel mounting where tools or fingers might contact the front face; the enclosure itself must provide the overall IP rating for washdown or outdoor environments. Maximum power dissipation is 10 W — a modest thermal load that keeps internal panel temperature rise manageable even in a densely packed distribution section.

Frequently asked questions

What is the depth of 3VA2110-6JP36-0AA0?

86 mm (3.39 in), which is the standard depth for this SENTRON 3VA frame size.

MPN