Skip to main content
Siemens 3VA2110-6JQ36-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-6JQ36-0AA0 SENTRON MCCB, 100 A, 242 kA

MPN3VA2110-6JQ36-0AA0
Active

Siemens SENTRON 3VA2110-6JQ36-0AA0, molded case circuit breaker, 3-pole, 100 A, ETU560 electronic trip, 242 kA at 240 V, line protection version.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2110-6JQ36-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2110-6JQ36-0AA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.10 W
3VA2110-6JQ36-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560
Overcurrent protection functionLSIG
Ground-fault monitoringSummation current formation L-conductor
3VA2110-6JQ36-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2110-6JQ36-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2110-6JQ36-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2110-6JQ36-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this 100 A MCCB carries

The Siemens SENTRON 3VA2110-6JQ36-0AA0 is a 3-pole molded case circuit breaker rated for 100 A continuous current across the full ambient range from 40 °C through 70 °C — no derating needed up to that ceiling. Breaking capacity hits 242 kA at 240 V, 187 kA at 415/440 V, and still holds 121 kA at 500 V, so it handles high-fault utility feeds or transformer secondaries without cascading upstream.

The optional motor drive (listed as a product extension) allows remote charging for motor-operated switchgear applications.

The 100 A rating at 70 °C means this breaker can sit in a warm panel — near a transformer or drive — without you having to oversize the frame. The ETU560 electronic trip gives you curve-shaping flexibility (LSIG) that a thermal-magnetic can't match, and the built-in ground-fault monitoring (summation current) saves adding an external GF relay for most line-to-ground protection schemes.

Frequently asked questions

Where can I buy 3VA2110-6JQ36-0AA0 and get a price?

This part is sourced and quoted to order against an RFQ through our independent distribution channel. Availability and current pricing are confirmed at quote time.

What is the depth of 3VA2110-6JQ36-0AA0?

The listed depth is 86 mm (3.39 in).

What compliance documentation does Siemens provide for this MCCB?

The evidence does not list specific compliance documents (RoHS, REACH, UL, IEC) for this order code. Standard SENTRON 3VA series documentation typically includes IEC 60947-2 and UL 489 declarations; verify the exact certificate set with your local Siemens support.

MPN
3VA2110-6JQ36-0AA0