Skip to main content
Siemens 3VA2110-7HL36-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-7HL36-0AA0 SENTRON MCCB, 100 A, 3-Pole, ETU3

MPN3VA2110-7HL36-0AA0
Active

Siemens SENTRON 3VA2110-7HL36-0AA0, molded case circuit breaker, line protection, 3-pole, 100 A, ETU320 electronic trip unit, breaking capacity 330 kA at 240 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2110-7HL36-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2110-7HL36-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.10 W
3VA2110-7HL36-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA2110-7HL36-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2110-7HL36-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2110-7HL36-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2110-7HL36-0AA0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2110-7HL36-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current of 100 A across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. That 100 A is the assigned permanent current Iu, so it handles the full load without a temperature haircut in a warm panel. The breaking capacity is substantial: 330 kA at 240 V AC, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3.7 kA at 690 V — so it clears high-fault currents on the secondary side of a large transformer or in a heavy industrial distribution board without cascading upstream.

Panel fit and protection

The breaker measures 105 mm wide, 181 mm tall, and 86 mm deep — a standard SENTRON 3VA frame size that drops into the same panel footprint as other 3VA2110 variants.

Frequently asked questions

Where can I buy 3VA2110-7HL36-0AA0 and how is it quoted?

This MCCB is sourced to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — no stock count or price is published here.

What is the breaking capacity of 3VA2110-7HL36-0AA0 at different voltages?

At 240 V AC it breaks 330 kA; at 415 V and 440 V, 242 kA; at 500 V, 187 kA; and at 690 V, 3.7 kA. That covers most industrial distribution voltages from low to medium fault levels.

Does 3VA2110-7HL36-0AA0 drop into a panel wired for 3VA2110-7HK42-0AA0?

Both are 3-pole SENTRON 3VA2110 frame breakers with the same 105 mm width, so the mechanical footprint and bus-bar spacing are identical. The difference is the trip unit and rating — this one is a 100 A ETU320, while the 3VA2110-7HK42-0AA0 carries a different rating and trip curve. Verify the trip settings match the downstream protection study before swapping.

MPN
3VA2110-7HL36-0AA0