Skip to main content
Siemens 3VA2110-7MN32-0BB0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-7MN32-0BB0 SENTRON MCCB, 100 A, 3-Pole, ETU3

MPN3VA2110-7MN32-0BB0

Siemens SENTRON 3VA2110-7MN32-0BB0, molded case circuit breaker, motor protection version, 3-pole, 100 A, ETU350M electronic trip unit, breaking capacity 330 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2110-7MN32-0BB0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionMotor protection
3VA2110-7MN32-0BB0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V3.8 kA
Power loss, max.10 W
3VA2110-7MN32-0BB0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M
3VA2110-7MN32-0BB0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2110-7MN32-0BB0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
3VA2110-7MN32-0BB0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2110-7MN32-0BB0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.1 in
Width (in)4.1 in

Product details

What it is and what it does

The Siemens 3VA2110-7MN32-0BB0 is a SENTRON molded case circuit breaker (MCCB) configured for motor protection — the product version is explicitly Motor Protection, not a plain feeder breaker. It carries a rated continuous current Iu of 100 A across the full ambient range from 40 °C to 70 °C, no derating needed in a warm panel. The electronic trip unit is an ETU350M, which means you get adjustable overload and short-circuit protection curves plus phase failure detection — the phase failure detection flag is set to Yes, so it will trip on a lost phase, which is exactly what you want on a motor circuit to prevent single-phasing. Breaking capacity is voltage-dependent: 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3.8 kA at 690 V. Those numbers tell you this breaker is built for high-fault locations — think transformer secondaries or large motor control centers where the available fault current is substantial.

Motor duty and panel fit

Rated motor-switching power is 30 kW at 230 V AC-3 and 55 kW at 400 V AC-3, so it covers a good range of medium induction motors on 400 V three-phase systems. The 3-pole design fits standard three-phase motor circuits. Dimensions are 105 mm wide, 181 mm tall, 86 mm deep — that width is the standard 105 mm frame size for this SENTRON 3VA2 series, so it occupies one 105 mm slot in a panel or switchboard. The front face carries an IP40 protection class, meaning tools or fingers won't reach live parts from the front, but the breaker is not sealed against moisture — it's for indoor panel mounting.

Frequently asked questions

Does 3VA2110-7MN32-0BB0 detect phase failure?

Yes, phase failure detection is enabled on this breaker — it will trip if one phase is lost, protecting the motor from single-phasing.

MPN
3VA2110-7MN32-0BB0