Skip to main content
Siemens 3VA2110-7MN36-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-7MN36-0AH0 SENTRON MCCB, 100 A, 330 kA

MPN3VA2110-7MN36-0AH0

Siemens SENTRON 3VA2110-7MN36-0AH0, molded case circuit breaker, 3-pole, 100 A, motor protection version, ETU350M electronic release, 330 kA interrupting at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2110-7MN36-0AH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionMotor protection
Basic switch (supplied) ref.3VA2110-7MN36-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA2110-7MN36-0AH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.75 W

Protection & Trip Unit

3VA2110-7MN36-0AH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M

Construction & Connection

3VA2110-7MN36-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2110-7MN36-0AH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA2110-7MN36-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2110-7MN36-0AH0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

What this 100 A MCCB is and what the ratings mean for fit

The Siemens SENTRON 3VA2110-7MN36-0AH0 is a 3-pole molded case circuit breaker in the motor protection version, rated for a continuous current Iu of 100 A. It uses the ETU350M electronic overcurrent release with phase-failure detection built in. The continuous current holds at 100 A from 40 °C up to 50 °C ambient, then derates to 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C. If your panel runs hot — say a sealed enclosure with drives — that 90 A at 70 °C is the number to size against, not the 100 A. The maximum power loss is 75 W, so factor that into the enclosure thermal budget. The auxiliary contact configuration is 2 auxiliary switches plus 1 trip alarm switch (HQ version), which is enough to signal the breaker state to a PLC or annunciator panel without adding a separate aux block.

Integration and panel fit — dimensions and mounting

The 3VA2110-7MN36-0AH0 measures 105 mm wide, 181 mm high, and 86 mm deep. The width of 105 mm is standard for a 3-pole 100 A frame in the SENTRON 3VA line.

Frequently asked questions

What is 3VA2110-7MN36-0AH0's listed depth?

The depth is 86 mm from the mounting surface to the front of the breaker.

Will 3VA2110-7MN36-0AH0 drop into a panel specified around a similar 3VA frame breaker?

Yes, the 105 mm width is common across the 3VA1 and 3VA2 frames at this rating, so the footprint matches without bus-bar or wiring changes.

MPN
3VA2110-7MN36-0AH0