Skip to main content
Siemens 3VA2110-7MN36-0CL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-7MN36-0CL0 SENTRON MCCB, 100 A, 3-Pole, Moto

MPN3VA2110-7MN36-0CL0

Siemens SENTRON 3VA2110-7MN36-0CL0, molded case circuit breaker, 3-pole, 100 A, motor protection design, with undervoltage release and phase failure detection.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2110-7MN36-0CL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21107MN360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22

Ratings

3VA2110-7MN36-0CL0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.12.5 W

Protection & Trip Unit

3VA2110-7MN36-0CL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2110-7MN36-0CL0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2110-7MN36-0CL0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4

Environmental

3VA2110-7MN36-0CL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2110-7MN36-0CL0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

MCCB for motor protection duty

The Siemens 3VA2110-7MN36-0CL0 is a SENTRON molded case circuit breaker (MCCB) designed specifically for motor protection, with a continuous current rating of 100 A across the full ambient temperature range from 40 °C to 70 °C — no derating needed up to the maximum operating temperature. Rated for 3-pole operation, it includes an undervoltage release and phase failure detection as integral functions, making it suited for protecting three-phase motor loads in industrial control panels where loss of a phase or voltage dip could damage the driven equipment.

Breaking capacity and selectivity

The interrupting rating reaches 330 kA at 240 V AC and 242 kA at 415 V and 440 V AC — figures that place this MCCB well into the high-fault category, suitable for installation close to large transformers or in heavy industrial distribution where available fault current is substantial. At 690 V AC the breaking capacity drops to 3.7 kA, so for 690 V applications this breaker is best used downstream of a current-limiting device or where the prospective fault current is known to be low.

Auxiliary switch complement and trip indication

The breaker ships with a built-in auxiliary switch block comprising 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch — a total of four signal contacts that can report breaker status and trip events back to a PLC or annunciator panel. A trip indicator is present on the front face, giving a local visual confirmation that the breaker has tripped on fault rather than being manually opened.

Physical footprint and panel fit

Dimensions are 181 mm high, 105 mm wide, and 86 mm deep — a standard 3-pole MCCB footprint that fits most SENTRON mounting bases and panel cutouts without requiring adapter plates. Maximum power dissipation is 12.5 W, which should be factored into the enclosure thermal budget when grouping multiple breakers in a sealed panel.

Frequently asked questions

What is the breaking capacity of 3VA2110-7MN36-0CL0 at 240 V?

The interrupting rating is 330 kA at 240 V AC.

Does this MCCB include phase failure protection?

Yes, phase failure detection is built in as a standard function.

What auxiliary contacts come with this breaker?

It includes 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch.

Where can I buy 3VA2110-7MN36-0CL0?

This part is sourced and quoted to order against an RFQ through independent distribution channels; availability and current pricing are confirmed at quote time.

MPN
3VA2110-7MN36-0CL0