At 70 °C ambient it still carries 90 A — useful for a crowded panel where the internal temperature runs high. Interrupting capacity is 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 52.5 kA at 690 V. That 330 kA figure at 240 V covers high-fault locations like a transformer secondary or a large UPS bypass; the 52.5 kA at 690 V is still substantial for most industrial 690 V distribution. Dimensions are 105 mm wide, 181 mm high, 86 mm deep — a standard SENTRON 3VA2 footprint that fits the same DIN-rail or screw-mount pattern as the rest of the 3VA2 family.
Maximum power loss is 75 W — factor that into the panel thermal budget if you are grouping several breakers in a sealed enclosure.
The 3VA2110-7MN36-0DC0 ships with 2 auxiliary switches (HQ type) pre-installed — order code 3VA9608-0BB25 for the auxiliary trip block. The undervoltage release (UVR) is integrated, so no separate coil wiring is needed for remote shunt-trip capability. The part carries a CE marking for the European market.