Skip to main content
Siemens 3VA2110-7MN36-0DH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-7MN36-0DH0 SENTRON MCCB, 100 A, 3-Pole, 330

MPN3VA2110-7MN36-0DH0

Siemens SENTRON 3VA2110-7MN36-0DH0, molded case circuit breaker, 3-pole, 100 A, interrupting rating 330 kA at 240 V, motor protection design, 86 x 105 x 181 mm.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2110-7MN36-0DH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21107MN360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA2110-7MN36-0DH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.12.5 W
3VA2110-7MN36-0DH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2110-7MN36-0DH0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2110-7MN36-0DH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA2110-7MN36-0DH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2110-7MN36-0DH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this MCCB delivers

The Siemens SENTRON 3VA2110-7MN36-0DH0 is a 3-pole molded case circuit breaker rated for 100 A continuous at 40 °C through 70 °C — no derating needed across that band. Its interrupting rating hits 330 kA at 240 V, dropping to 242 kA at 415 V and 440 V, then 187 kA at 500 V, and 3.7 kA at 690 V.

Motor protection and auxiliary features

This MCCB is explicitly designed for motor protection, with phase failure detection built in. The trip indicator confirms the breaker opened on a fault versus manual switching. Power loss maxes at 12.5 W, which keeps panel heat manageable in a dense enclosure.

Physical fit and mounting

The 86 mm depth leaves clearance for rear-connected busbars or cable lugs in a typical 200 mm deep enclosure.

Frequently asked questions

How do I get current pricing and availability for 3VA2110-7MN36-0DH0?

Submit an RFQ through this listing. We source and quote to order; availability and current pricing are confirmed at quote time.

What is the interrupting rating of 3VA2110-7MN36-0DH0 at 240 V?

330 kA at 240 V. It also carries 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3.7 kA at 690 V.

Does this MCCB include an undervoltage release?

Yes, it comes with an undervoltage release (UVR) as the auxiliary release, plus 2 auxiliary switches and 1 trip alarm switch.

MPN
3VA2110-7MN36-0DH0