Skip to main content
Siemens 3VA2110-7MN36-0DH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-7MN36-0DH0 SENTRON MCCB, 100 A, 3-Pole, 330

MPN3VA2110-7MN36-0DH0

Siemens SENTRON 3VA2110-7MN36-0DH0, molded case circuit breaker, 3-pole, 100 A, interrupting rating 330 kA at 240 V, motor protection design, 86 x 105 x 181 mm.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2110-7MN36-0DH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21107MN360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA2110-7MN36-0DH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.12.5 W

Protection & Trip Unit

3VA2110-7MN36-0DH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2110-7MN36-0DH0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2110-7MN36-0DH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA2110-7MN36-0DH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2110-7MN36-0DH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this MCCB delivers

The Siemens SENTRON 3VA2110-7MN36-0DH0 is a 3-pole molded case circuit breaker rated for 100 A continuous at 40 °C through 70 °C — no derating needed across that band. Its interrupting rating hits 330 kA at 240 V, dropping to 242 kA at 415 V and 440 V, then 187 kA at 500 V, and 3.7 kA at 690 V. That 330 kA figure at 240 V means it can safely clear a fault on a high-capacity transformer secondary or a large motor branch without the arc flash energy escalating — the kind of SCCR that lets you avoid a series-rated cascade upstream.

Motor protection and auxiliary features

This MCCB is explicitly designed for motor protection, with phase failure detection built in. It ships with an undervoltage release (UVR) and a 2-auxiliary-switch + 1 trip-alarm-switch HQ configuration — so you get remote status of the breaker state and trip cause without adding a separate module. The trip indicator confirms the breaker opened on a fault versus manual switching. Power loss maxes at 12.5 W, which keeps panel heat manageable in a dense enclosure.

Physical fit and mounting

Dimensions: 86 mm deep, 105 mm wide, 181 mm tall. That 105 mm width is standard for a 3-pole frame in the SENTRON 3VA family — it mounts on a DIN rail or screws into a panel baseplate. The 86 mm depth leaves clearance for rear-connected busbars or cable lugs in a typical 200 mm deep enclosure.

Frequently asked questions

How do I get current pricing and availability for 3VA2110-7MN36-0DH0?

Submit an RFQ through this listing. We source and quote to order; availability and current pricing are confirmed at quote time.

What is the interrupting rating of 3VA2110-7MN36-0DH0 at 240 V?

330 kA at 240 V. It also carries 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3.7 kA at 690 V.

Does this MCCB include an undervoltage release?

Yes, it comes with an undervoltage release (UVR) as the auxiliary release, plus 2 auxiliary switches and 1 trip alarm switch.

MPN
3VA2110-7MN36-0DH0