Siemens 3VA2110-7MN36-0HH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-7MN36-0HH0 SENTRON MCCB, 100 A, 3-Pole, Moto

MPN3VA2110-7MN36-0HH0

Siemens SENTRON 3VA2110-7MN36-0HH0, molded case circuit breaker, 3-pole, 100 A, motor protection design, phase failure detection, shunt trip STL, 2 aux switches + 1 trip alarm switch HQ.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2110-7MN36-0HH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21107MN360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA2110-7MN36-0HH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.10 W
3VA2110-7MN36-0HH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350M
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2110-7MN36-0HH0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2110-7MN36-0HH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA2110-7MN36-0HH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2110-7MN36-0HH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2110-7MN36-0HH0 is a 3-pole molded case circuit breaker rated for 100 A continuous current across the full 40 °C to 70 °C ambient range — no derating needed as the panel warms up near a motor starter stack. This is the motor-protection variant, with phase failure detection built in, so it catches a lost phase on a conveyor or pump drive before the winding overheats.

Short-circuit breaking capacity hits 330 kA at 240 V, 242 kA at 415 V and 440 V, and 187 kA at 500 V — numbers that put this MCCB well into the high-fault category for industrial distribution. The trip time band is 4 s minimum to 17 s maximum, giving the selectivity engineer room to coordinate with downstream breakers on a motor control center feeder.

Auxiliaries and release configuration

The basic switch assembly is order code 3VA21107MN360AA0, which means the aux block is integral, not a field-add-on. A voltage trigger is present; undervoltage release is not, so the shunt trip is the only remote-trip path.

Integration dimensions

Max power loss is 10 W, so ventilation in a sealed enclosure is advisable if multiple breakers are ganged.

Frequently asked questions

How do I get current pricing and availability for 3VA2110-7MN36-0HH0?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is the interrupting capacity of 3VA2110-7MN36-0HH0?

330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3.7 kA at 690 V.

Does 3VA2110-7MN36-0HH0 include a shunt trip?

Yes, it is factory-fitted with a shunt trip release (STL) plus two auxiliary switches and one trip alarm switch HQ.

MPN
3VA2110-7MN36-0HH0