Siemens SENTRON 3VA2110-7MQ36-0AC0, molded case circuit breaker, 3-pole, 100 A, motor protection, ETU860M electronic trip unit, 330 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2110-7MQ36-0AC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionMotor protection
3VA2110-7MQ36-0AC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V3.8 kA
Power loss, max.10 W
3VA2110-7MQ36-0AC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU860M
3VA2110-7MQ36-0AC0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2110-7MQ36-0AC0 — Accessories & Functions
ParameterValue
Communication functionYes
Measurement functionYes
Motor drive optionYes
3VA2110-7MQ36-0AC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2110-7MQ36-0AC0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.1 in
Width (in)4.1 in

Product details

MCCB for motor protection with ETU860M

The interrupting ratings are substantial: 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3.8 kA at 690 V — that's enough SCCR headroom to coordinate downstream of a large transformer or generator without cascading upstream. This breaker includes phase failure detection and ground fault monitoring via summation current formation on the L-conductor, so it catches a lost phase or a ground leak before the motor cooks. The ETU860M also supports communication functions, meaning it can talk to a higher-level control system for trip data and remote reset — useful on a line where you want to log fault events without sending someone to the panel.

Power loss is a maximum of 10 W, so heat buildup in a densely packed panel is manageable.

Frequently asked questions

Where can I buy 3VA2110-7MQ36-0AC0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — send the order code for a firm quote.

What is the closest functional second-source for 3VA2110-7MQ36-0AC0?

The peer MPNs 5SQ2370-2YA05, 5SQ2370-2YA04, and 5SQ2370-2YA01 are listed as functional alternatives, but they are not direct drop-in replacements without verifying the trip unit settings and physical footprint against your existing panel layout.

What are the key ratings of 3VA2110-7MQ36-0AC0?

It is a 3-pole 100 A MCCB with an ETU860M electronic trip unit, interrupting ratings of 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3.8 kA at 690 V. It handles motor loads up to 30 kW at 230 V AC-3 and 55 kW at 400 V AC-3.

MPN
3VA2110-7MQ36-0AC0