The 3-pole unit delivers a short-circuit breaking capacity of 330 kA at 240 V, dropping to 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3.7 kA at 690 V.
The undervoltage release is absent (no voltage trigger), and there is no ground-fault monitoring version, no communication function, and no phase failure detection — this is a straightforward thermal-magnetic motor protector, not a smart breaker. Power loss is rated at a maximum of 10 W, which is modest for a 100 A frame and helps keep enclosure internal temperature rise manageable.