Interrupting capacity hits 330 kA at 240 V, 242 kA at 415 V, and still 187 kA at 500 V; at 690 V it drops to 3.7 kA — that last number tells you this breaker is sized for 400 V class distribution, not 690 V motor feeders. Three poles, 300 A minimum to 1 500 A maximum frame rating — the 100 A thermal-magnetic trip is set at the factory. Undervoltage release (UVR) is built in, so if your control voltage drops, the breaker opens without a separate shunt trip module.

Siemens 3VA2110-7MS36-0BL0 SENTRON MCCB, 100 A, 240V 330 kA
Siemens SENTRON 3VA2110-7MS36-0BL0, molded case circuit breaker, 3-pole, 100 A, interrupting 330 kA at 240 V, starter protection design, undervoltage release.
Specifications
| Parameter | Value |
|---|---|
| Product designation | Molded case circuit breaker |
| Brand / range | SENTRON |
| Basic switch (supplied) ref. | 3VA21107MS360AA0 |
| Integrated auxiliary / alarm switch ref. | 3VA9988-0AB22 |
| Parameter | Value |
|---|---|
| Number of poles | 3 |
| Rated operational voltage Ue (AC) | 690 V |
| Rated insulation voltage Ui | 800 V |
| Current at 40 °C | 100 A |
| Current at 45 °C | 100 A |
| Current at 50 °C | 100 A |
| Current at 55 °C | 100 A |
| Current at 60 °C | 100 A |
| Current at 65 °C | 100 A |
| Current at 70 °C | 100 A |
| Switching capacity class | C |
| Breaking capacity at 240 V | 330 kA |
| Breaking capacity at 415 V | 242 kA |
| Breaking capacity at 440 V | 242 kA |
| Breaking capacity at 500 V | 187 kA |
| Breaking capacity at 690 V | 3.7 kA |
| Power loss, max. | 12.5 W |
| Parameter | Value |
|---|---|
| Overcurrent release (trip unit) type | ETU310M |
| Overcurrent protection function | I |
| Ground-fault monitoring | Without |
| Grounding protection function | No |
| Parameter | Value |
|---|---|
| Main circuit connection type | double-sided box terminal |
| Main circuit connector arrangement | Front terminal |
| Protection class (IP), front | IP40 |
| Parameter | Value |
|---|---|
| Undervoltage release | Yes |
| Voltage trigger | No |
| Trip indicator | Yes |
| Communication function | No |
| Measurement function | No |
| Motor drive option | Yes |
| Auxiliary CO contacts | 4 |
| Parameter | Value |
|---|---|
| Operating temperature, max. | 70 °C |
| Operating temperature, min. | -25 °C |
| Storage temperature, max. | 80 °C |
| Storage temperature, min. | -40 °C |
| Parameter | Value |
|---|---|
| Mechanical service life (operating cycles), typ. | 25 000 |
| Height | 181 mm |
| Width | 105 mm |
| Depth | 86 mm |
| Height (in) | 7.13 in |
| Width (in) | 4.13 in |
| Depth (in) | 3.39 in |
Product details
Frequently asked questions
What is the interrupting capacity of 3VA2110-7MS36-0BL0 at 240 V?
330 kA at 240 V. At 415 V and 440 V it's 242 kA; at 500 V it's 187 kA; at 690 V it drops to 3.7 kA. That 690 V number is the weak point — this breaker is designed for 400 V class distribution, not 690 V motor feeders.
What is the continuous current rating and does it derate with temperature?
100 A continuous from 40 °C all the way up to 70 °C — no derating needed across that entire operating range. That's unusual for an MCCB; most start losing capacity above 40 °C.
Where can I buy 3VA2110-7MS36-0BL0 and how is it quoted?
Sourced and quoted to order through independent industrial distribution. Submit an RFQ for current pricing and availability — confirmed at quote time, not before.