Skip to main content
Siemens 3VA2110-7MS36-0DA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-7MS36-0DA0 SENTRON MCCB, 100 A, 330 kA at 24

MPN3VA2110-7MS36-0DA0

Siemens SENTRON 3VA2110-7MS36-0DA0, molded case circuit breaker, 3-pole, 100 A rated continuous current, 330 kA breaking capacity at 240 V, starter protection version with ETU310M electronic release and undervoltage release.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2110-7MS36-0DA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionStarter protection
Basic switch (supplied) ref.3VA2110-7MS36-0AA0
3VA2110-7MS36-0DA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.75 W
3VA2110-7MS36-0DA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU310M
3VA2110-7MS36-0DA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2110-7MS36-0DA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2110-7MS36-0DA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2110-7MS36-0DA0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

Integrator's note — 3VA2110-7MS36-0DA0

The Siemens SENTRON 3VA2110-7MS36-0DA0 is a 3-pole molded case circuit breaker rated for 100 A continuous current at 40 °C, with a breaking capacity of 330 kA at 240 V and 242 kA at 415 V. This is the starter protection variant, fitted with an ETU310M electronic overcurrent release and an integrated undervoltage release (UVR).

The 330 kA at 240 V and 242 kA at 415 V place this breaker in the high-interrupting category for a 100 A frame. For selectivity studies, the ETU310M release provides adjustable overload and short-circuit pickup, allowing coordination with downstream breakers in a distribution panel. The 800 V rated insulation voltage (Ui) supports 690 V line-to-line systems, where the breaking capacity drops to 52.5 kA — still adequate for most industrial 690 V bus feeds.

The breaker carries 100 A continuously up to 50 °C ambient, then derates to 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C. Maximum power loss is 75 W.

Frequently asked questions

What is the breaking capacity of 3VA2110-7MS36-0DA0 at different voltages?

330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 52.5 kA at 690 V.

What overcurrent release does this breaker use?

It uses the ETU310M electronic release, which provides adjustable overload and short-circuit protection settings.

Does 3VA2110-7MS36-0DA0 include an undervoltage release?

Yes, it is factory-fitted with an undervoltage release (UVR) as the auxiliary release.

Where can I buy 3VA2110-7MS36-0DA0?

This part is sourced and quoted to order against an RFQ through independent industrial distribution. Availability and current pricing are confirmed at quote time.

MPN
3VA2110-7MS36-0DA0