Skip to main content
Siemens 3VA2110-7MS36-0KL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-7MS36-0KL0 SENTRON MCCB, 100 A, 330 kA at 24

MPN3VA2110-7MS36-0KL0

Siemens SENTRON 3VA2110-7MS36-0KL0, molded case circuit breaker, 3-pole, starter protection design, 100 A continuous rating, 330 kA breaking capacity at 240 V, 86 mm depth, 105 mm width, 181 mm height.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2110-7MS36-0KL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21107MS360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22

Ratings

3VA2110-7MS36-0KL0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.10 W

Protection & Trip Unit

3VA2110-7MS36-0KL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU310M
Overcurrent protection functionI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2110-7MS36-0KL0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2110-7MS36-0KL0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4

Environmental

3VA2110-7MS36-0KL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2110-7MS36-0KL0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this MCCB is and where it lands

The Siemens 3VA2110-7MS36-0KL0 is a SENTRON molded case circuit breaker (MCCB) designed specifically for starter protection — meaning it's built to sit ahead of a motor starter combination, not just a general distribution feeder. Three poles, 100 A continuous at 40 °C all the way up to 70 °C (no derate needed in that band), and a breaking capacity that starts at 330 kA at 240 V and drops to 242 kA at 415/440 V, then 187 kA at 500 V, and 3.7 kA at 690 V. That 330 kA at 240 V tells you this thing is meant for high-fault locations — think transformer secondaries or large bus risers where the available fault current is brutal.

What the ratings mean for your panel

At 105 mm wide, 181 mm tall, and 86 mm deep, this MCCB fits standard SENTRON mounting footprints — the 86 mm depth is the key number for enclosure depth planning, especially if you're retrofitting into an existing panel with limited gland-plate clearance. The 100 A rating is flat across the full 40–70 °C ambient range, so you don't lose headroom in a hot enclosure. That's unusual and saves you from having to oversize the frame just because the panel runs warm.

Auxiliary and release configuration

Comes with a shunt trip release (STL) and a full auxiliary switch complement: 2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ. That means you get remote trip capability and status feedback without adding external modules. The basic switch order code is 3VA21107MS360AA0 — useful if you're ordering spare switch blocks separately.

Frequently asked questions

Where can I buy 3VA2110-7MS36-0KL0 and get current pricing?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is the breaking capacity of this MCCB at different voltages?

330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3.7 kA at 690 V.

Does this breaker include a shunt trip or undervoltage release?

It includes a shunt trip release (STL) but no undervoltage release.

MPN
3VA2110-7MS36-0KL0