Skip to main content
Siemens 3VA2110-8HL42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-8HL42-0AA0 SENTRON MCCB, 100A 4-Pole, 440kA

MPN3VA2110-8HL42-0AA0
Active

Siemens SENTRON 3VA2110-8HL42-0AA0, molded case circuit breaker, 4-pole, 100 A, line protection, ETU320, interrupting rating 440 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2110-8HL42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2110-8HL42-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classL
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V330 kA
Breaking capacity at 440 V330 kA
Breaking capacity at 500 V220 kA
Breaking capacity at 690 V53 kA
Power loss, max.7.7 W
3VA2110-8HL42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2110-8HL42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2110-8HL42-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2110-8HL42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-40 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2110-8HL42-0AA0 — Mechanical
ParameterValue
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.1 in
Width (in)5.5 in
Depth (in)3.4 in

Product details

What this MCCB does for your panel

Its ETU320 electronic trip unit gives you adjustable long-time delay (0.5 to 17 s) and N-conductor protection configurable to OFF, 50%, or 100% of phase current, so it handles both three-phase and single-phase line-to-neutral faults in a single package. The interrupting ratings are substantial: 440 kA at 240 V, 330 kA at 415 V, and 53 kA at 690 V, meaning it can clear high-fault-current events without cascading upstream in most distribution panels.

The 3VA2110-8HL42-0AA0 measures 181 mm high, 140 mm wide, and 86 mm deep — a compact 4-pole MCCB that fits standard distribution panelboards. Maximum power loss is 7.7 W, which is modest enough that you don't need forced ventilation in a typical 200 A panel, but worth checking against your enclosure's thermal budget if you're packing several breakers side by side.

Frequently asked questions

Where can I buy 3VA2110-8HL42-0AA0 and get a price?

This part is sourced through our independent distribution channel and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — submit an RFQ and we'll respond with a firm price and lead time.

What is 3VA2110-8HL42-0AA0's interrupting rating at 240 V?

It carries 440 kA at 240 V, which is the highest short-circuit current it can safely interrupt at that voltage. At 415 V and 440 V it's 330 kA; at 690 V it's 53 kA.

What trip unit does this MCCB use?

It uses the ETU320 electronic trip unit with adjustable long-time delay from 0.5 to 17 seconds and N-conductor protection configurable to OFF, 50%, or 100% of phase current.

MPN