Skip to main content
Siemens 3VA2110-8JQ42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-8JQ42-0AA0 SENTRON MCCB, 100 A, 150–1200 A T

MPN3VA2110-8JQ42-0AA0
Active

Siemens SENTRON 3VA2110-8JQ42-0AA0, molded case circuit breaker, 4-pole, 100 A continuous, adjustable trip 150–1200 A, 440 kA at 240 V, 86 mm depth, 140 mm width, 181 mm height.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2110-8JQ42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA2110-8JQ42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classL
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V330 kA
Breaking capacity at 440 V330 kA
Breaking capacity at 500 V220 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.7.7 W

Protection & Trip Unit

3VA2110-8JQ42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560
Overcurrent protection functionLSIG
Ground-fault monitoringSummation current formation L + N conductor
Grounding protection functionYes

Construction & Connection

3VA2110-8JQ42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2110-8JQ42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2110-8JQ42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2110-8JQ42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

What it is and what it does

The Siemens SENTRON 3VA2110-8JQ42-0AA0 is a 4-pole molded case circuit breaker (MCCB) designed for line protection. It carries a continuous rated current of 100 A and an adjustable thermal-magnetic trip unit covering 150 A to 1,200 A. The interrupting ratings climb to 440 kA at 240 V and 330 kA at 415/440 V, tapering to 52.5 kA at 690 V. That SCCR headroom means it can sit close to a large transformer or high-fault bus without needing a current-limiting fuse upstream — a real advantage when you're coordinating a distribution panel. The trip unit has a 20 A minimum setting and a 100 A full-scale value, so it's field-adjustable for a range of feeder or branch loads without swapping the breaker. Ground-fault monitoring works via summation current formation on L+N, and the communication function is built in — no separate module required for status or remote trip signalling. Rated insulation voltage is 800 V, and the breaker is good for operation from -25 °C to 70 °C, with storage down to -40 °C. Power loss runs 7.7 W at full load.

Sizing and selectivity

For a panel OEM or MRO planner: this breaker is rated 100 A continuous from 40 °C all the way up to 70 °C — no derating curve to chase in a hot enclosure. The adjustable trip range (150–1,200 A) lets you set it for a 150 A feeder or crank it up for a 1,200 A main, but the continuous current rating of 100 A is the hard limit for the frame and lugs. If your load draws more than 100 A steady, you need a larger frame. The 4-pole construction means it switches all three phases plus neutral, which is standard for North American 120/208 V or 277/480 V wye systems where you need the neutral switched or monitored. The 800 V rated insulation voltage covers 690 V class installations with margin.

Physical fit

Dimensions are 86 mm deep, 140 mm wide, and 181 mm tall. That's a standard MCCB footprint for the 100 A frame size — it'll drop into a 4-pole mounting base or panel cutout without surprises. The width is the key dimension for multi-breaker lineup spacing; 140 mm is typical for this class, so it fits alongside other 3VA or comparable 100 A frames on the same DIN rail or mounting plate.

Frequently asked questions

How do I get current pricing and availability for 3VA2110-8JQ42-0AA0?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through our independent distribution network — no stock figures or price are shown here because they change daily.

What is 3VA2110-8JQ42-0AA0's listed depth on this component line?

The depth is 86 mm (3.39 in), with a width of 140 mm (5.51 in) and height of 181 mm (7.13 in).

Will 3VA2110-8JQ42-0AA0 drop into a panel that was specified around 3VA2163-8HM32-0AA0 without rewiring?

Both are 4-pole SENTRON 3VA MCCBs in the same 100 A frame class, so the physical footprint and mounting pattern are identical. The key difference is the trip range: this breaker adjusts from 150 A to 1,200 A, while the 3VA2163 variant uses a different trip unit. If the existing panel's wiring and bus bars are sized for a 100 A continuous frame, the swap is mechanical — no re-drilling or re-bussing needed. But verify the trip curve and settings match your protection coordination study before swapping.

What compliance documentation does this brand provide for 3VA2110-8JQ42-0AA0 (RoHS, REACH, UL, IEC)?

As a Siemens SENTRON product, this MCCB carries CE marking for the European market and is designed to IEC 60947-2. UL and CSA listings are standard for the 3VA family, and RoHS/REACH declarations are available from Siemens' documentation portal. Specific certification marks for this exact order code should be confirmed from the manufacturer's declaration of conformity.

MPN
3VA2110-8JQ42-0AA0