MCCB for line protection — 100 A continuous, 440 kA interrupting at 240 V
The interrupting capacity is 440 kA at 240 V, dropping to 330 kA at 415 V and 440 V, 220 kA at 500 V, and 52.5 kA at 690 V — these numbers govern the available fault current the breaker can clear without failure. This breaker includes a communication function and ground-fault monitoring via summation current formation on the L + N conductor. Maximum power loss is 7.7 W.