Skip to main content
Siemens 3VA2110-8JQ46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-8JQ46-0AA0 SENTRON MCCB, 100 A, 4-Pole, 440

MPN3VA2110-8JQ46-0AA0
Active

Siemens SENTRON 3VA2110-8JQ46-0AA0, molded case circuit breaker, 4-pole, 100 A continuous rating, line protection design, interrupting capacity 440 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2110-8JQ46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2110-8JQ46-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classL
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V330 kA
Breaking capacity at 440 V330 kA
Breaking capacity at 500 V220 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.7.7 W
3VA2110-8JQ46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560
Overcurrent protection functionLSIG
Ground-fault monitoringSummation current formation L + N conductor
Grounding protection functionYes
3VA2110-8JQ46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2110-8JQ46-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2110-8JQ46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2110-8JQ46-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

MCCB for line protection — 100 A continuous, 440 kA interrupting at 240 V

The interrupting capacity is 440 kA at 240 V, dropping to 330 kA at 415 V and 440 V, 220 kA at 500 V, and 52.5 kA at 690 V — these numbers govern the available fault current the breaker can clear without failure. This breaker includes a communication function and ground-fault monitoring via summation current formation on the L + N conductor. Maximum power loss is 7.7 W.

Frequently asked questions

How do I get current pricing and availability for 3VA2110-8JQ46-0AA0?

Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through independent distribution channels.

What is 3VA2110-8JQ46-0AA0's interrupting capacity at 415 V?

330 kA at 415 V, matching the rating at 440 V. At 240 V it reaches 440 kA; at 690 V it is 52.5 kA.

Does 3VA2110-8JQ46-0AA0 include ground-fault monitoring?

Yes, it has ground-fault monitoring via summation current formation on the L + N conductor.

MPN
3VA2110-8JQ46-0AA0