Skip to main content
Siemens 3VA2110-8KQ32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-8KQ32-0AA0 SENTRON MCCB, 100 A, 3-Pole, Line

MPN3VA2110-8KQ32-0AA0
Active

Siemens SENTRON 3VA2110-8KQ32-0AA0, molded case circuit breaker, 3-pole, 100 A continuous rating, line protection design, 440 kA breaking capacity at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2110-8KQ32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA2110-8KQ32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classL
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V330 kA
Breaking capacity at 440 V330 kA
Breaking capacity at 500 V220 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.7.7 W

Protection & Trip Unit

3VA2110-8KQ32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU860
Overcurrent protection functionLSIG
Ground-fault monitoringSummation current formation L-conductor
Grounding protection functionYes

Construction & Connection

3VA2110-8KQ32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2110-8KQ32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2110-8KQ32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2110-8KQ32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What the 100 A continuous rating means for your panel

The Siemens SENTRON 3VA2110-8KQ32-0AA0 is a 3-pole molded case circuit breaker rated for 100 A continuous current across the full ambient temperature range from 40 °C to 70 °C — no derating needed up to that ceiling. That 100 A holds steady at every 5 °C increment, so it's sized for a 100 A feeder or branch circuit in a warm enclosure without recalculating the thermal curve. The 800 V rated insulation voltage gives headroom for 480 V and 600 V class systems; the 440 kA interrupting rating at 240 V drops to 330 kA at 415 V and 52.5 kA at 690 V, so verify the available fault current at your service voltage before committing the BOM line.

Breaking capacity curve — what trips up specifiers

This MCCB carries a communication function and ground-fault monitoring via summation current formation on the L-conductor, so it's not a bare thermal-magnetic — it's a communicating, ground-fault-capable breaker for line protection. The 7.7 W maximum power loss is low enough that ventilation in a standard IP2X enclosure is sufficient; no forced cooling required. Dimensions are 105 mm wide, 181 mm tall, 86 mm deep — fits standard Siemens 3VA panel cutouts and busbar systems without adapter plates.

Frequently asked questions

How do I get current pricing and availability for 3VA2110-8KQ32-0AA0?

This part is sourced and quoted to order against an RFQ. Submit a request through the storefront; availability and current pricing are confirmed at quote time.

Will 3VA2110-8KQ32-0AA0 drop into a panel specified around 3VA1110-5ED32-0AA0 without rewiring?

The 3VA2110-8KQ32-0AA0 is a 3-pole, 100 A MCCB with communication and ground-fault monitoring — a different feature set than the 3VA1110-5ED32-0AA0. Both are SENTRON 3VA platform breakers sharing the same 105 mm width, 181 mm height, and 86 mm depth footprint, so they fit the same panel cutout and busbar spacing. However, the 3VA2110 carries additional wiring for the communication function and ground-fault summation current transformer, so the panel must have those connections provisioned. Verify the auxiliary wiring diagram before swapping.

What compliance documentation does this brand provide for 3VA2110-8KQ32-0AA0?

Siemens SENTRON MCCBs are designed to IEC 60947-2 and UL 489 standards. The manufacturer provides RoHS and REACH declarations, CE and UKCA markings, and a declaration of conformity. Specific documentation is available on request with the RFQ.

MPN