Skip to main content
Siemens 3VA2110-8KQ36-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2110-8KQ36-0AA0 SENTRON MCCB, 100 A, 3-Pole, 440

MPN3VA2110-8KQ36-0AA0
Active

Siemens SENTRON 3VA2110-8KQ36-0AA0, molded case circuit breaker, 3-pole, 100 A continuous, line protection, 440 kA interrupting capacity at 240 V, with ground-fault monitoring and communication function.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2110-8KQ36-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA2110-8KQ36-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classL
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V330 kA
Breaking capacity at 440 V330 kA
Breaking capacity at 500 V220 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.7.7 W

Protection & Trip Unit

3VA2110-8KQ36-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU860
Overcurrent protection functionLSIG
Ground-fault monitoringSummation current formation L-conductor
Grounding protection functionYes

Construction & Connection

3VA2110-8KQ36-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2110-8KQ36-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2110-8KQ36-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2110-8KQ36-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What it is and what the ratings mean

The Siemens 3VA2110-8KQ36-0AA0 is a SENTRON molded case circuit breaker (MCCB) rated for 100 A continuous current at up to 70 °C ambient — meaning it holds that rating across the full operating temperature range without derating, which is unusual and simplifies panel design for warm environments like enclosed switchboards or near furnace lines. Three-pole construction with a 440 kA interrupting capacity at 240 V — that is a very high fault-clearing rating, sized for large industrial service entrances or distribution points where available fault current is severe; at 690 V it still interrupts 52.5 kA, covering most 690 V industrial systems. Designed specifically for line protection (not motor or generator protection), so the trip curve and accessories are optimized for cable and busbar protection in main or branch feeders.

Dimensions and panel fit

Measures 105 mm wide, 181 mm high, 86 mm deep — fits standard MCCB panel cutouts and DIN-rail or fixed-mount enclosures; the 86 mm depth is shallow enough for most 200 mm deep enclosures with room for wiring gutters.

Ground-fault and communication capability

Includes ground-fault monitoring via summation current formation on the L-conductor — meaning it detects leakage current without a separate GFCI module, useful for personnel protection in wet or corrosive environments. Communication function is built in, enabling remote monitoring and trip indication over a bus system — no external adapter needed for basic status reporting.

MPN
3VA2110-8KQ36-0AA0