What this MCCB does in the panel
This MCCB delivers 440 kA at 240 V, 330 kA at both 415 V and 440 V, 220 kA at 500 V, and 52.5 kA at 690 V.
Ground-fault and communication
Ground-fault monitoring uses summation current formation on L + N conductors — it sees the vector sum and trips on residual current, not just phase imbalance.
Those dimensions matter for panel layout — the 140 mm width on a 4-pole frame means it occupies roughly four 35 mm DIN-rail module spaces. The 86 mm depth keeps it clear of shallow enclosure doors.