Skip to main content
Siemens 3VA2116-0HL36-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2116-0HL36-0AA0 MCCB, 160 A, 440 kA

MPN3VA2116-0HL36-0AA0
Active

Siemens SENTRON series, Molded case circuit breaker, 3VA2116-0HL36-0AA0, 3-pole, 160 A continuous, 440 kA at 415 V, ETU320 release, line protection.

$499.11Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2116-0HL36-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2116-0HL36-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classE
Breaking capacity at 415 V440 kA
Breaking capacity at 690 V187 kA
Power loss, max.19.7 W
3VA2116-0HL36-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2116-0HL36-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2116-0HL36-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2116-0HL36-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2116-0HL36-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2116-0HL36-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated for 160 A continuous current, designed for line protection in industrial power distribution panels. It carries a massive 440 kA breaking capacity at 415 V AC and 187 kA at 690 V AC — that means it can safely interrupt a fault current up to that level without the arc escaping or the case rupturing, which is critical for high-fault installations like transformer secondaries or large motor control centers. The ETU320 electronic trip unit handles the overcurrent release, giving you adjustable long-time, short-time, and instantaneous protection curves — not just a fixed thermal-magnetic bimetal.

Fit and panel integration

Footprint is 105 mm wide, 181 mm tall, 86 mm deep — standard for a 160 A frame MCCB, so it drops into most existing panel layouts without re-drilling the mounting plate.

If you're freezing a BOM for a new line, this part is a safe bet; no PCN or LTB watch needed today.

Frequently asked questions

What trip unit does 3VA2116-0HL36-0AA0 use?

ETU320 electronic trip unit with adjustable long-time, short-time, and instantaneous protection curves.

MPN
3VA2116-0HL36-0AA0