Skip to main content
Siemens 3VA2116-0HM32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2116-0HM32-0AA0 SENTRON MCCB, 160 A, ETU330, 3-Po

MPN3VA2116-0HM32-0AA0
Active

Siemens SENTRON 3VA2116-0HM32-0AA0, molded case circuit breaker, 3-pole, 160 A continuous, ETU330 electronic trip unit, 440 kA breaking capacity at 415 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2116-0HM32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2116-0HM32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classE
Breaking capacity at 415 V440 kA
Breaking capacity at 690 V187 kA
Power loss, max.19.7 W
3VA2116-0HM32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU330
Overcurrent protection functionLIG
Ground-fault monitoringSummation current formation L-conductor
Grounding protection functionYes
3VA2116-0HM32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2116-0HM32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2116-0HM32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2116-0HM32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The ETU330 electronic trip unit is adjustable from 32 A to 160 A full-scale, letting you dial in the exact overload threshold without swapping the breaker. For a 415 V secondary distribution board fed by a large transformer, this gives selectivity headroom downstream.

No undervoltage release or communication module is integrated on this variant.

Integration notes

Mounts in a standard SENTRON panel cutout. The IP40 front protection rating means it is suitable for indoor switchgear where tools are required to access live parts — not for washdown environments. Verify the ETU330 settings (32 A minimum, 160 A maximum) against the load before commissioning — the dials are field-adjustable but require the front cover open.

Frequently asked questions

Where can I buy 3VA2116-0HM32-0AA0 and how is it quoted?

This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time.

What are the key ratings of 3VA2116-0HM32-0AA0?

Rated continuous current is 160 A, adjustable trip range 32 A to 160 A via the ETU330 electronic trip unit. Breaking capacity is 440 kA at 415 V and 187 kA at 690 V. Rated insulation voltage is 800 V. Three poles, 105 mm wide.

Will 3VA2116-0HM32-0AA0 drop into a panel specified around 3VA2116-5JP32-0AE0?

Both are 3-pole SENTRON MCCBs with the same 105 mm width and 181 mm height, so the mounting footprint is identical. The difference is in the trip unit and accessories — verify the ETU330 settings and any auxiliary contact requirements before substituting.

What compliance documentation does this breaker carry?

As a SENTRON product, it is designed to meet IEC 60947-2 and UL 489 standards for molded case circuit breakers. Specific certification marks (UL, CSA, CE) should be verified against the nameplate on the specific unit received.

MPN
3VA2116-0HM32-0AA0