3VA2116-0KP46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2116-0KP46-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classE
Breaking capacity at 415 V440 kA
Breaking capacity at 690 V187 kA
Power loss, max.19.7 W
3VA2116-0KP46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2116-0KP46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2116-0KP46-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts0
3VA2116-0KP46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2116-0KP46-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

SENTRON 3VA2 with ETU850 — 160 A, 440 kA at 415 V

The Siemens SENTRON 3VA2116-0KP46-0AA0 is a 4-pole molded case circuit breaker (MCCB) rated for 160 A continuous current, with an ETU850 electronic trip unit and a maximum breaking capacity of 440 kA at 415 V AC. This is a line-protection design, meaning it's specified for feeder and main breaker positions in distribution panels, not for direct motor starting.

Trip unit and protection flexibility

The ETU850 is an electronic overcurrent release with communication capability. It supports adjustable N-conductor protection from OFF through 20% to 100% of the phase rating, which matters for panels feeding mixed single-phase and three-phase loads where neutral current can exceed phase imbalance. The trip indicator is absent, so fault-event logging relies on the communication interface rather than a local mechanical flag. Power loss at full rated current is 19.7 W — a figure to include in enclosure thermal calculations if the breaker is in a sealed, uncooled cabinet.

Front-face protection is IP40, adequate for enclosed distribution boards but not for washdown areas. Dimensions are 181 mm height, 140 mm width, 86 mm depth.

Frequently asked questions

Where can I buy 3VA2116-0KP46-0AA0 and what is the lead time?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for the current lead time.

What is the breaking capacity of 3VA2116-0KP46-0AA0 at 415 V?

440 kA at 415 V AC. At 690 V AC it is rated 187 kA.

Does 3VA2116-0KP46-0AA0 have communication capability?

Yes, the ETU850 trip unit includes a communication function. This allows remote monitoring and parameterization via the SENTRON communication platform.

What is the continuous current rating of 3VA2116-0KP46-0AA0?

160 A continuous, and this rating holds without derating across the full operating temperature range from 40 °C to 70 °C (through,).