SENTRON 3VA2116-0KQ42-0AA0 — 160 A MCCB with ETU860 Electronic Trip
Its ETU860 electronic trip unit provides adjustable overload protection from 240 A up to 1 600 A, with a fixed full-scale value of 160 A — meaning the trip curve is set for the breaker's frame, not the load.
Trip Unit and Protection Configuration
The ETU860 electronic trip unit supports ground-fault monitoring via summation current formation on the L + N conductor — a common requirement for TN-S or TT systems where you need residual current detection without a separate RCD. The N-conductor protection is adjustable from OFF to 20%–100% of the phase rating, giving flexibility for systems where the neutral is undersized or needs to be switched off. No undervoltage release or voltage trip is fitted as standard — those would be add-on accessories.
Thermal Performance and Environmental Range
That is unusual for a molded case breaker; most start derating above 40 °C. The maximum power loss is 19.7 W, which is moderate for a 160 A frame and manageable in a ventilated enclosure. The IP40 front protection means it is suited for indoor panel mounting, not washdown environments.
As a Siemens SENTRON product, the 3VA2116-0KQ42-0AA0 carries the usual compliance documentation for industrial MCCBs: CE marking for the European market, UL/CSA listing for North America, and RoHS/REACH declarations. Specific certificate numbers should be verified against the project's local code requirements.