Skip to main content
Siemens 3VA2116-5HL36-0JL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2116-5HL36-0JL0 SENTRON MCCB, 160 A, 187 kA at 24

MPN3VA2116-5HL36-0JL0

Siemens SENTRON 3VA2116-5HL36-0JL0, molded case circuit breaker, 3-pole, 160 A, line protection, ETU320 electronic trip unit, shunt trip, 187 kA at 240 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2116-5HL36-0JL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2116-5HL36-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22
3VA2116-5HL36-0JL0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C154 A
Current at 60 °C148 A
Current at 65 °C142 A
Current at 70 °C136 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V79 kA
Breaking capacity at 690 V4.25 kA
Power loss, max.25.5 W
3VA2116-5HL36-0JL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2116-5HL36-0JL0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2116-5HL36-0JL0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4
3VA2116-5HL36-0JL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2116-5HL36-0JL0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

Interrupting capacity and continuous rating

The Siemens SENTRON 3VA2116-5HL36-0JL0 is a 3-pole molded case circuit breaker rated for 160 A continuous current at 40 °C. Its interrupting capacity reaches 187 kA at 240 V AC, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 4.25 kA at 690 V.

Trip unit and auxiliary configuration

The auxiliary contact block includes 2 auxiliary switches plus 1 trip alarm switch and 1 electrical alarm switch (HQ configuration), giving the panel builder a full set of status signals back to the PLC or SCADA without adding a separate contactor stack.

Thermal derating and environmental limits

The breaker holds its full 160 A rating from 40 °C through 50 °C. Above that, derate linearly: 154 A at 55 °C, 148 A at 60 °C, 142 A at 65 °C, 136 A at 70 °C. Operating ambient range is -25 °C to 70 °C; storage range is -40 °C to 80 °C. Maximum power dissipation is 25.5 W — relevant for panel heat load calculations in a sealed enclosure.

Frequently asked questions

What is the interrupting capacity of this MCCB at 240 V?

187 kA at 240 V AC, which is the highest rating on this breaker — suitable for high-fault-current installations near transformers or service entrances.

What trip unit does the 3VA2116-5HL36-0JL0 use?

The ETU320 electronic trip unit, providing adjustable protection curves for long-time, short-time, instantaneous, and ground-fault elements.

Does this breaker include a shunt trip?

Yes, it includes a shunt trip (STL) auxiliary release for remote tripping, plus 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch.

Where can I buy the 3VA2116-5HL36-0JL0 and how is it quoted?

Sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock figures are published on this listing.

MPN
3VA2116-5HL36-0JL0