Skip to main content
Siemens 3VA2116-5HL42-0AB0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2116-5HL42-0AB0 SENTRON MCCB, 160 A, 4-Pole, 187

MPN3VA2116-5HL42-0AB0

Siemens SENTRON 3VA2116-5HL42-0AB0, molded case circuit breaker, 4-pole, 160 A, ETU320 electronic release, 187 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2116-5HL42-0AB0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2116-5HL42-0AB0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V76 kA
Breaking capacity at 690 V3.8 kA
Power loss, max.25.5 W
3VA2116-5HL42-0AB0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2116-5HL42-0AB0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2116-5HL42-0AB0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
3VA2116-5HL42-0AB0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2116-5HL42-0AB0 — Mechanical
ParameterValue
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.1 in
Width (in)5.5 in

Product details

The Siemens SENTRON 3VA2116-5HL42-0AB0 is a 4-pole molded case circuit breaker rated for a continuous current of 160 A across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. The ETU320 electronic trip unit gives adjustable long-time delay (0.5 s to 17 s at tr max) and configurable N-conductor protection (OFF, 50%, 100%). That makes it suitable for distribution panels where coordination with downstream breakers matters — you shape the curve, not just accept a fixed thermal-magnetic characteristic.

Footprint is 140 mm wide by 181 mm tall by 86 mm deep — the 140 mm width is a standard 4-pole frame size for this SENTRON generation. Maximum power dissipation is 25.5 W. In a densely packed enclosure, that heat needs to be factored into the thermal budget — especially if the breaker is loaded near its 160 A continuous rating.

Frequently asked questions

Where can I buy 3VA2116-5HL42-0AB0 and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time.

What is 3VA2116-5HL42-0AB0's listed depth (86 mm) on this component line?

The depth is 86 mm, which is the dimension from the mounting surface to the front face of the breaker — relevant for enclosure depth clearance.

What is 3VA2116-5HL42-0AB0's listed width (140 mm) on this component line?

The width is 140 mm, which corresponds to the standard 4-pole frame width for this SENTRON MCCB series.

Will 3VA2116-5HL42-0AB0 drop into a panel that was specified around 3VA2116-5HL32-0AK0 without rewiring?

Both share the same 4-pole frame and 160 A rating, so the mechanical footprint and busbar centers are identical. The difference is in the trip unit — the HL42 carries an ETU320 electronic release, while the HL32 uses a different release variant. Panel cutout and wiring pattern are compatible, but verify the trip curve coordination before swapping.

MPN
3VA2116-5HL42-0AB0