Skip to main content
Siemens 3VA2116-5HL42-0KF0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2116-5HL42-0KF0 SENTRON MCCB, 160 A, 4-Pole, 187

MPN3VA2116-5HL42-0KF0

Siemens SENTRON 3VA2 molded case circuit breaker, 4-pole, 160 A continuous, line protection, 187 kA breaking at 240 V, shunt trip (STL), 1 aux + 1 trip alarm HQ.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2116-5HL42-0KF0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21165HL420AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA2116-5HL42-0KF0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.25.5 W

Protection & Trip Unit

3VA2116-5HL42-0KF0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2116-5HL42-0KF0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2116-5HL42-0KF0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2116-5HL42-0KF0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2116-5HL42-0KF0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

What this MCCB delivers — and what it doesn't

The Siemens 3VA2116-5HL42-0KF0 is a SENTRON molded case circuit breaker sized for line protection in 4-pole, 160 A continuous duty. The continuous current holds flat at 160 A from 40 °C through 70 °C — no derating needed across that span, which simplifies panel sizing in warm enclosures. Breaking capacity is the headline: 187 kA at 240 V, 121 kA at 415 V and 440 V, dropping to 75.6 kA at 500 V, and 3.7 kA at 690 V. That 187 kA figure at 240 V means it can interrupt a fault of that magnitude without upstream cascading — critical for high-available-fault-current distribution panels. It ships with a shunt trip (STL) and one auxiliary switch plus one trip alarm switch (HQ). No undervoltage release, no ground-fault monitoring, no communication function — this is a pure line-protection breaker, not a multifunction device.

Panel fit and environmental limits

Dimensions are 86 mm deep, 140 mm wide, 181 mm high — fits standard MCCB panel cutouts for the 3VA2 frame. Operating range is -25 °C to 70 °C; storage from -40 °C to 80 °C. Power loss at rated load is 25.5 W maximum — account for that in enclosure thermal calculations. The basic switch supplied is order code 3VA21165HL420AA0.

Frequently asked questions

Who supplies 3VA2116-5HL42-0KF0 and how is it quoted for volume purchases?

This part is sourced through independent distribution. Volume pricing and lead time are confirmed at quote time against an RFQ.

What is the breaking capacity of 3VA2116-5HL42-0KF0 at 240 V?

187 kA at 240 V, dropping to 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V.

Does 3VA2116-5HL42-0KF0 include a shunt trip or undervoltage release?

It includes a shunt trip (STL). No undervoltage release is fitted.

What auxiliary switches come with 3VA2116-5HL42-0KF0?

One auxiliary switch plus one trip alarm switch (HQ).

MPN