Skip to main content
Siemens 3VA2116-5HL46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2116-5HL46-0AA0 SENTRON MCCB, 160 A, 4-Pole, 187

MPN3VA2116-5HL46-0AA0
Active

Siemens SENTRON 3VA2116-5HL46-0AA0, molded case circuit breaker, 4-pole, 160 A continuous, ETU320 electronic trip unit, 187 kA at 240 V, 86 mm depth, 140 mm width, 181 mm height.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2116-5HL46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA2116-5HL46-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.25.5 W

Protection & Trip Unit

3VA2116-5HL46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2116-5HL46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2116-5HL46-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2116-5HL46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2116-5HL46-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

What it is and what it does

The Siemens SENTRON 3VA2116-5HL46-0AA0 is a 4-pole molded case circuit breaker (MCCB) rated for 160 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. It carries an ETU320 electronic trip unit, which means the protection curve is adjustable for selective coordination downstream. The breaker is designed for line protection (cable and busbar feeders) in distribution panels.

Breaking capacity — what the numbers mean

The interrupting ratings climb to 187 kA at 240 V AC, drop to 121 kA at 415 V and 440 V, then to 75.6 kA at 500 V, and settle at 3.7 kA at 690 V. That 187 kA figure at 240 V is the headline — it means this breaker can safely clear a bolted fault on a low-voltage transformer secondary without upstream fuses needing to open. At 690 V the 3.7 kA rating is still adequate for most motor-circuit faults, but if your system has a high available fault current above that voltage, you need a current-limiting upstream device.

Panel fit and mounting

The breaker measures 86 mm deep by 140 mm wide by 181 mm high — a standard 4-pole MCCB footprint. The front face carries an IP40 rating. No undervoltage release or shunt trip is built in.

Frequently asked questions

Will 3VA2116-5HL46-0AA0 drop into a panel that was specified around 3VA2116-5JP32-0AE0 without rewiring?

Both are 4-pole SENTRON 3VA breakers with the same physical footprint (86 mm deep, 140 mm wide, 181 mm high), so mechanical fit is identical. The electrical difference is the trip unit: the -5HL46-0AA0 carries an ETU320 electronic release, while the -5JP32-0AE0 uses a different trip curve. Verify the protection settings match your coordination study before swapping.

MPN
3VA2116-5HL46-0AA0