Skip to main content
Siemens 3VA2116-5HM46-0AA0 — Molded Case Circuit Breakers (MCCB)

SENTRON 3VA2116-5HM46-0AA0 MCCB, 160 A, 187 kA at 240 V

MPN3VA2116-5HM46-0AA0
Active

SENTRON 3VA2116-5HM46-0AA0, molded case circuit breaker, 4-pole, 160 A, ETU330 electronic trip, 187 kA at 240 V interrupting rating.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2116-5HM46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA2116-5HM46-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V76 kA
Breaking capacity at 690 V3.8 kA
Power loss, max.25.5 W

Protection & Trip Unit

3VA2116-5HM46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU330
Overcurrent protection functionLIG
Ground-fault monitoringSummation current formation L + N conductor

Construction & Connection

3VA2116-5HM46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2116-5HM46-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2116-5HM46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2116-5HM46-0AA0 — Mechanical
ParameterValue
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.1 in
Width (in)5.5 in
Depth (in)3.4 in

Product details

What this MCCB is and what it handles

The SENTRON 3VA2116-5HM46-0AA0 is a 4-pole molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current of 160 A across the full operating range from 40 °C to 70 °C with no derating required — that's the same 160 A at 70 °C as at 40 °C, which simplifies panel design in warm enclosures. Interrupting capacity is 187 kA at 240 V, dropping to 121 kA at 415 V or 440 V, 76 kA at 500 V, and 3.8 kA at 690 V — so for most 400 V-class industrial feeds it clears 121 kA fault current without cascading upstream.

Trip unit and protection features

The overcurrent release is an ETU330 electronic trip unit with adjustable long-time pickup (I_g) from 0.3 s to 160 A and short-time pickup (I_i) up to 1 600 A. Ground-fault monitoring uses summation current formation on L+N — adjustable OFF, 50%, or 100% of the N-conductor protection setting. No communication function onboard — this is a standalone protection device, not a smart breaker. Optional motor drive available as a field-fit accessory.

Mounting and integration

Dimensions are 140 mm wide, 181 mm tall, 86 mm deep — fits standard MCCB panel cutouts and busbar systems. Front face carries IP40 protection, suitable for enclosed panel mounting where no water ingress is expected. Storage range spans -40 °C to 80 °C; operating range -25 °C to 70 °C. Maximum power loss is 25.5 W — factor that into enclosure thermal calculations.

Frequently asked questions

Where can I buy 3VA2116-5HM46-0AA0 and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote — availability and current pricing are confirmed at quote time.

What is the interrupting rating at 415 V?

At 415 V the interrupting capacity is 121 kA.

What trip unit does this MCCB use?

It uses an ETU330 electronic overcurrent release with adjustable long-time and short-time settings.

MPN
3VA2116-5HM46-0AA0