Skip to main content
Siemens 3VA2116-5HN32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2116-5HN32-0AA0 SENTRON MCCB, 160 A, 3-Pole, 187

MPN3VA2116-5HN32-0AA0
Active

Siemens SENTRON 3VA2 series, molded case circuit breaker, 3VA2116-5HN32-0AA0, 3-pole, 160 A continuous, ETU350 electronic trip unit, 187 kA at 240 V, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2116-5HN32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA2116-5HN32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.25.5 W

Protection & Trip Unit

3VA2116-5HN32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2116-5HN32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2116-5HN32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2116-5HN32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2116-5HN32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

Siemens 3VA2116-5HN32-0AA0 — 160 A SENTRON MCCB with ETU350 Trip Unit

The Siemens 3VA2116-5HN32-0AA0 is a SENTRON 3VA2 series molded case circuit breaker (MCCB) rated for 160 A continuous current across the full 40 °C to 70 °C ambient range — no derating needed up to that ceiling. That flat thermal curve is the headline feature for panel builders: you can load the frame to its nameplate 160 A in a warm enclosure without recalculating the ampacity. Three-pole construction with an ETU350 electronic overcurrent release. The ETU350 provides LI (long-time and instantaneous) protection, adjustable via rotary dials on the front face. No ground-fault monitoring, no undervoltage release, no communication module — this is a straight line-protection breaker for distribution panels where the upstream coordination is already set. Breaking capacity is 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V. The 690 V figure looks low because the 3VA2 frame is not optimized for high-voltage distribution — this breaker lives in 240–480 V switchgear where its SCCR headroom is generous.

Panel Fit and Mounting

Dimensions are 105 mm wide, 181 mm high, 86 mm deep. The 105 mm width is the standard 3-pole MCCB footprint for this frame size — it occupies three 35 mm DIN-rail modules plus a small margin. IP40 on the front face means the breaker is protected against tools and wires >1 mm entering the enclosure opening, but the body itself is not sealed; mount inside a panel with a door. No trip indicator on the front, so fault isolation requires reading the handle position or checking downstream loads. For a service tech swapping a tripped breaker, the absence of a visual flag means you verify the trip by handle feel and load-side voltage check.

Sourcing and Lifecycle

Rated insulation voltage is 800 V, and the storage temperature range is -40 °C to 80 °C. Maximum power loss at rated current is 25.5 W — a useful figure for enclosure thermal calculations when packing multiple breakers in a confined panel.

Frequently asked questions

Where can I buy 3VA2116-5HN32-0AA0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the continuous current rating of this MCCB?

The continuous current rating is 160 A, and it holds that rating across the full 40 °C to 70 °C ambient range without derating.

What type of trip unit does this breaker use?

It uses the ETU350 electronic overcurrent release, which provides adjustable long-time and instantaneous (LI) protection. No ground-fault or undervoltage release is included.

MPN
3VA2116-5HN32-0AA0