Skip to main content
Siemens 3VA2116-5HN32-0HA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2116-5HN32-0HA0 SENTRON MCCB, 160 A, 187 kA at 24

MPN3VA2116-5HN32-0HA0

Siemens SENTRON 3VA2116-5HN32-0HA0, molded case circuit breaker, 3-pole, 160 A rated continuous current, 187 kA interrupting capacity at 240 V AC, line protection, ETU350 electronic trip unit, shunt trip release.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2116-5HN32-0HA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2116-5HN32-0AA0
3VA2116-5HN32-0HA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C154 A
Current at 60 °C148 A
Current at 65 °C142 A
Current at 70 °C136 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V79 kA
Breaking capacity at 690 V4.25 kA
Power loss, max.25.5 W
3VA2116-5HN32-0HA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
3VA2116-5HN32-0HA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2116-5HN32-0HA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2116-5HN32-0HA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2116-5HN32-0HA0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

It carries a rated continuous current Iu of 160 A and an interrupting capacity of 187 kA at 240 V AC, which drops to 121 kA at 415 V and 4.25 kA at 690 V. A shunt trip release (STL) is integrated for remote tripping via a control signal — useful for emergency-stop or supervisory shutdown circuits.

Panel integration and physical fit

Thermal derating and ambient limits

The 160 A rating holds up to 50 °C. Above that, derate linearly: 154 A at 55 °C, 148 A at 60 °C, 142 A at 65 °C, and 136 A at 70 °C. Maximum power loss is 25.5 W — account for that heat in a sealed enclosure.

Frequently asked questions

How do I get current pricing and availability for 3VA2116-5HN32-0HA0?

Pricing and stock are confirmed at quote time against an RFQ through our independent distribution channel. Submit a request for a current quote.

What is 3VA2116-5HN32-0HA0's depth?

86 mm. This is the dimension from the mounting plane to the front face.

What is 3VA2116-5HN32-0HA0's width?

105 mm, which occupies three 35 mm DIN-rail module spaces.

Will 3VA2116-5HN32-0HA0 drop into a panel specified around 3VA1110-5EE32-0JA0 without rewiring?

No, the two breakers are different frame sizes and ratings. The 3VA1110-5EE32-0JA0 is a 100 A frame; this 3VA2116-5HN32-0HA0 is a 160 A frame with different dimensions and terminal spacing. Panel cutouts and busbar connections would need to be re-evaluated.

What compliance documentation does Siemens provide for 3VA2116-5HN32-0HA0?

The manufacturer provides RoHS and REACH declarations, as well as IEC/UL certification documentation for the SENTRON series. Specific certificates are available on request.

MPN
3VA2116-5HN32-0HA0