Siemens 3VA2116-5HN36-0AF0 — Molded Case Circuit Breakers (MCCB)

3VA2116-5HN36-0AF0 SENTRON MCCB, 160 A, 187 kA at 240 V

MPN3VA2116-5HN36-0AF0

Siemens SENTRON 3VA2116-5HN36-0AF0, 3-pole molded case circuit breaker, 160 A, ETU350 electronic overcurrent release, line protection, 187 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2116-5HN36-0AF0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2116-5HN36-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA2116-5HN36-0AF0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C154 A
Current at 60 °C148 A
Current at 65 °C142 A
Current at 70 °C136 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V79 kA
Breaking capacity at 690 V4.25 kA
Power loss, max.25.5 W

Protection & Trip Unit

3VA2116-5HN36-0AF0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout

Construction & Connection

3VA2116-5HN36-0AF0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2116-5HN36-0AF0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2116-5HN36-0AF0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2116-5HN36-0AF0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

SENTRON 3VA2116-5HN36-0AF0 — 160 A MCCB with ETU350 Release

The Siemens SENTRON 3VA2116-5HN36-0AF0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current of 160 A at 40 °C through 50 °C. The ETU350 electronic overcurrent release provides adjustable trip settings, making this breaker suitable for feeder and main switchboard applications where selectivity and coordination are required. The 187 kA breaking capacity at 240 V (121 kA at 415 V and 440 V) means it can safely interrupt high-fault currents without cascading upstream — a key spec for high-capacity transformer secondaries or large motor control centers.

Thermal Derating and Application Context

The 160 A rating holds flat from 40 °C to 50 °C, then derates to 154 A at 55 °C, 148 A at 60 °C, 142 A at 65 °C, and 136 A at 70 °C. For a panel with an ambient of 55 °C — common in a non-conditioned electrical room — the breaker is effectively a 154 A device. The maximum operating temperature of 70 °C and storage range of -40 °C to 80 °C cover most industrial environments. The 25.5 W maximum power loss at rated current matters for thermal management inside a sealed enclosure; account for this when sizing ventilation or calculating internal temperature rise.

Auxiliary Contacts and Release Configuration

This variant ships with one auxiliary switch and one trip alarm switch (HQ type) — enough for remote status indication of breaker position and fault tripping. There is no undervoltage release, no shunt trip, no ground-fault monitoring, and no communication function. The overcurrent release is the ETU350, an electronic trip unit with adjustable long-time, short-time, instantaneous, and ground-fault (if enabled) protection curves. The basic switch supplied is the 3VA2116-5HN36-0AA0, which is the core switching mechanism without the electronic trip unit.

Frequently asked questions

Where can I buy 3VA2116-5HN36-0AF0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA2116-5HN36-0AF0 at 415 V?

The breaking capacity is 121 kA at 415 V and 440 V, 187 kA at 240 V, 79 kA at 500 V, and 4.25 kA at 690 V.

What is the rated current of 3VA2116-5HN36-0AF0?

The rated current is 160 A from 40 °C to 50 °C, derating to 154 A at 55 °C, 148 A at 60 °C, 142 A at 65 °C, and 136 A at 70 °C.

MPN
3VA2116-5HN36-0AF0