Siemens 3VA2116-5HN36-0AJ0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2116-5HN36-0AJ0 SENTRON MCCB, 160 A, 3-Pole, 187

MPN3VA2116-5HN36-0AJ0

Siemens SENTRON 3VA2116-5HN36-0AJ0, molded case circuit breaker, 3-pole, 160 A rated continuous current, 187 kA breaking capacity at 240 V AC, line protection design.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2116-5HN36-0AJ0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21165HN360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB11
3VA2116-5HN36-0AJ0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.25.5 W
3VA2116-5HN36-0AJ0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2116-5HN36-0AJ0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2116-5HN36-0AJ0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA2116-5HN36-0AJ0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2116-5HN36-0AJ0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2116-5HN36-0AJ0 is a 3-pole molded case circuit breaker rated for 160 A continuous current at 40 °C through 70 °C — no derating needed across that span, which simplifies panel design in warm enclosures. Breaking capacity reaches 187 kA at 240 V AC, 121 kA at 415/440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V. It is a line-protection device (no ground-fault monitoring, no undervoltage release, no communication module) — a straightforward main or feeder breaker for distribution panels, motor control centers, and switchboards.

Breaking capacity — what the voltage steps tell you

The 187 kA at 240 V is the headline number, but the 121 kA at 415 V is the one that matters for most European and Asian 400 V class panels. At 500 V it still holds 75.6 kA — enough for most industrial 480 V feeds in North America. The drop to 3.7 kA at 690 V means this frame is not intended for high-impedance 690 V systems; if your line side is 690 V with significant fault current, you need a larger frame or a current-limiting upstream device.

Physical fit and auxiliary wiring

No communication function, no undervoltage release, no shunt trip — if you need remote trip or status over a bus, this is not the variant. The supplied basic switch order code is 3VA21165HN360AA0, which is the internal switching mechanism; you order the complete breaker as 3VA2116-5HN36-0AJ0.

Frequently asked questions

Where can I buy 3VA2116-5HN36-0AJ0?

This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time.

What are the key ratings for 3VA2116-5HN36-0AJ0?

It is a 3-pole molded case circuit breaker rated 160 A continuous (no derating from 40 °C to 70 °C), with breaking capacity of 187 kA at 240 V, 121 kA at 415/440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V. Insulation voltage is 800 V.

Will 3VA2116-5HN36-0AJ0 drop into a panel specified for 3VA2116-5HL32-0AK0?

Both are 3VA2 frame breakers with the same physical footprint (105 mm wide, 181 mm tall, 86 mm deep), so the mechanical fit is identical. The difference is in the internal trip unit and auxiliary configuration — verify the trip curve and accessory count match your BOM before substituting.

What compliance documentation does Siemens provide for this MCCB?

The evidence does not list specific compliance certificates (RoHS, REACH, UL, IEC) for this order code. Siemens SENTRON breakers typically carry IEC 60947-2 and UL 489 certifications, but confirm the exact documentation package with your order.