Skip to main content
Siemens 3VA2116-5HN36-0BH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2116-5HN36-0BH0 MCCB, 160 A, 3-Pole, 187 kA at 24

MPN3VA2116-5HN36-0BH0

Siemens SENTRON 3VA series molded case circuit breaker, 3VA2116-5HN36-0BH0, 160 A, 3-pole, line protection with undervoltage release and auxiliary switches.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2116-5HN36-0BH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21165HN360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA2116-5HN36-0BH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.28 W

Protection & Trip Unit

3VA2116-5HN36-0BH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2116-5HN36-0BH0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2116-5HN36-0BH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA2116-5HN36-0BH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2116-5HN36-0BH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this MCCB is and what it does

The Siemens SENTRON 3VA2116-5HN36-0BH0 is a 3-pole molded case circuit breaker (MCCB) rated for 160 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. It's designed for line protection, meaning it sits at the incoming feed of a distribution panel or as the main disconnect for a machine, not for motor-circuit protection (no adjustable thermal or magnetic trip settings for motor starting). The interrupting capacity tells you where it can go: 187 kA at 240 V AC, 121 kA at 415 V or 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V. That 187 kA at 240 V is the headline number — it clears a massive fault without blowing apart, which matters when you're feeding a panel with high available fault current from a utility transformer or a large generator.

What the ratings mean for your panel

The 160 A frame is a common size for a main breaker in a panelboard or for feeding a sub-panel. The 3-pole configuration handles three-phase systems. The breaker includes an undervoltage release, 2 auxiliary switches, and 1 trip alarm switch.

Where to get it and what to expect

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time. The operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C.

Frequently asked questions

What auxiliary switches does this breaker include?

It includes 2 auxiliary switches and 1 trip alarm switch (HQ type), plus an undervoltage release (UVR).

What are the physical dimensions of 3VA2116-5HN36-0BH0?

105 mm wide, 181 mm tall, 86 mm deep (4.13" by 7.13" by 3.39").

MPN