Skip to main content
Siemens 3VA2116-5HN36-0DH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2116-5HN36-0DH0 Circuit Breaker, 55kA @ 415V, 160

MPN3VA2116-5HN36-0DH0

Siemens 3VA2 IEC frame 160, breaking capacity class M, Icu=55kA @ 415V, 3-pole, line protection ETU350 LSI, In=160A, overload protection Ir=63A...160A, short-circuit protection Isd=1.5...10 x Ir, Ii=10 x In, clamp connection, undervoltage release 208-230V AC 50/60Hz, 2 auxiliary switches HQ, 1 trip alarm switch HQ.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Product details

The Siemens 3VA2116-5HN36-0DH0 is a 3-pole IEC molded-case circuit breaker in the 3VA2 frame, rated 160 A continuous with an Icu of 55 kA at 415 V AC — that is the breaking capacity class M, meaning it safely interrupts faults up to that level without upstream cascading, sized for main or heavy feeder protection in industrial panels.

Protection and trip unit

Fitted with an ETU350 electronic trip unit offering LSI protection: long-time pickup Ir adjustable from 63 A to 160 A, short-time pickup Isd from 1.5 to 10 x Ir, and instantaneous pickup Ii fixed at 10 x In. That gives you selective coordination flexibility — set Isd high enough to ride through downstream faults, or tighten it for close-coupled protection on sensitive loads. The undervoltage release (UVR) operates on 208-230 V AC 50/60 Hz, so the breaker trips automatically when control voltage drops — standard for emergency-stop or safety-shutdown circuits where loss of pilot power must open the main contacts.

Auxiliary and signaling

Two HQ auxiliary switches and one HQ trip alarm switch are built in — the HQ designation indicates high-quantity contacts (typically 2 N.O. + 2 N.C. per switch), giving you status feedback for remote monitoring and a dedicated alarm contact that changes state only on a trip event, not on manual open.

Frequently asked questions

What is the breaking capacity of this breaker?

Icu is 55 kA at 415 V AC, which is the class M breaking capacity for the 3VA2 frame — suitable for high-fault industrial mains.

What protection functions does the ETU350 provide?

LSI: long-time (Ir 63–160 A), short-time (Isd 1.5–10 x Ir), and instantaneous (Ii 10 x In).

Where can I buy 3VA2116-5HN36-0DH0 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

MPN