Siemens 3VA2116-5HN36-0JA0 SENTRON MCCB, 160 A, 187 kA at 24

MPN3VA2116-5HN36-0JA0

Siemens SENTRON 3VA2116-5HN36-0JA0, molded case circuit breaker, 3-pole, 160 A, 187 kA at 240 V, ETU350 trip unit, shunt trip.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2116-5HN36-0JA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2116-5HN36-0AA0
3VA2116-5HN36-0JA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C154 A
Current at 60 °C148 A
Current at 65 °C142 A
Current at 70 °C136 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V79 kA
Breaking capacity at 690 V4.25 kA
Power loss, max.25.5 W
3VA2116-5HN36-0JA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
3VA2116-5HN36-0JA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2116-5HN36-0JA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2116-5HN36-0JA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2116-5HN36-0JA0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

The overcurrent release is an ETU350 electronic trip unit, adjustable for coordination studies. Breaking capacity hits 187 kA at 240 V, 121 kA at 415 V, and 79 kA at 500 V; at 690 V it drops to 4.25 kA, so watch your system voltage when sizing for fault current.

The breaker holds 160 A straight through 50 °C ambient; above that it derates to 154 A at 55 °C, 148 A at 60 °C, 142 A at 65 °C, and 136 A at 70 °C.

Frequently asked questions

What is the breaking capacity of 3VA2116-5HN36-0JA0 at 415 V?

At 415 V the breaker is rated for 121 kA breaking capacity. At 240 V it reaches 187 kA; at 500 V it drops to 79 kA; at 690 V it is 4.25 kA.

What trip unit does 3VA2116-5HN36-0JA0 use?

It uses an ETU350 electronic overcurrent release. The breaker also includes a shunt trip (STL) auxiliary release but no undervoltage release, no auxiliary contacts, and no communication function.

Where can I buy 3VA2116-5HN36-0JA0?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

MPN
3VA2116-5HN36-0JA0