Skip to main content
Siemens 3VA2116-5HN36-0JL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2116-5HN36-0JL0 SENTRON MCCB, 160 A, 3-Pole, 187

MPN3VA2116-5HN36-0JL0

Siemens SENTRON 3VA2116-5HN36-0JL0, molded case circuit breaker, 3-pole, 160 A continuous, 187 kA interrupting at 240 V, line protection design with shunt trip (STL) and auxiliary switches.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2116-5HN36-0JL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21165HN360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22

Ratings

3VA2116-5HN36-0JL0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.25.5 W

Protection & Trip Unit

3VA2116-5HN36-0JL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2116-5HN36-0JL0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2116-5HN36-0JL0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4

Environmental

3VA2116-5HN36-0JL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2116-5HN36-0JL0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this MCCB delivers — and what it doesn't

The Siemens 3VA2116-5HN36-0JL0 is a SENTRON molded case circuit breaker (MCCB) rated for 160 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling, which simplifies panel thermal budgeting. Interrupting capacity is 187 kA at 240 V, dropping to 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V — the 690 V figure is low, so confirm fault current at that voltage before specifying. This is a line-protection design (not motor-protection) with no undervoltage release, no ground-fault monitoring, and no communication function — it is a straightforward thermal-magnetic MCCB with a shunt trip (STL) and a complement of auxiliary switches: 2 auxiliary + 1 trip alarm + 1 electrical alarm switch HQ.

Physical fit and panel integration

Dimensions are 105 mm wide, 181 mm high, and 86 mm deep — a 3-pole frame that occupies standard MCCB panel space; verify the mounting footprint against your existing backplate or DIN-rail adapter. Maximum power loss is 25.5 W — factor this into enclosure ventilation calculations, especially in sealed cabinets.

Frequently asked questions

What is 3VA2116-5HN36-0JL0's listed depth?

The depth is 86 mm.

What is 3VA2116-5HN36-0JL0's listed width?

The width is 105 mm.

Will 3VA2116-5HN36-0JL0 drop into a panel specified around 3VA1110-5EF32-0AM0 without rewiring?

The 3VA2116-5HN36-0JL0 is a 3-pole 160 A MCCB with a shunt trip and auxiliary switches; the 3VA1110-5EF32-0AM0 is a different frame rating and accessory set — physical fit and wiring depend on the specific panel layout and should be verified against both datasheets.

MPN
3VA2116-5HN36-0JL0