Siemens 3VA2116-5JQ32-0BC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2116-5JQ32-0BC0 SENTRON MCCB, 160 A, 187 kA at 24

MPN3VA2116-5JQ32-0BC0

Siemens SENTRON 3VA2116-5JQ32-0BC0, molded case circuit breaker, 3-pole, 160 A, 187 kA interrupting capacity at 240 VAC, line protection design with undervoltage release and communication function.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2116-5JQ32-0BC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21165JQ320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2116-5JQ32-0BC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.28 W

Protection & Trip Unit

3VA2116-5JQ32-0BC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560
Overcurrent protection functionLSIG
Ground-fault monitoringSummation current formation L-conductor
Grounding protection functionYes

Construction & Connection

3VA2116-5JQ32-0BC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2116-5JQ32-0BC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2116-5JQ32-0BC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2116-5JQ32-0BC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

Siemens SENTRON 3VA2116-5JQ32-0BC0 is a 3-pole molded case circuit breaker rated for line protection, with a full-scale current of 160 A that holds flat across the ambient range — still 160 A at 70 °C, not derated until you push past that. The interrupting capacity hits 187 kA at 240 V, dropping to 121 kA at 415 V and 440 V, then 75.6 kA at 500 V, and 3.7 kA at 690 V. That 187 kA figure at 240 V tells you this breaker is sized for high-fault panels where the upstream transformer can dump serious energy — think service entrance or main feeder duty in industrial switchgear. The 105 mm width and 181 mm height fit standard SENTRON MCCB panel cutouts; depth at 86 mm leaves room behind the gland plate for cable bending radius. Undervoltage release (UVR) is built in, and the auxiliary switch pack provides two HQ-rated contacts for status feedback to the PLC or safety circuit. Communication function is present on this variant — no separate comm module needed for basic trip-signal reporting.

Integration & Mounting

Mounts on a DIN rail or direct panel-mount via the SENTRON base plate. The 3-pole footprint with 105 mm width means three of these side by side consume 315 mm of rail — plan your enclosure fill factor accordingly. Power loss is 28 W maximum at rated load, so account for that heat in a sealed cabinet; forced ventilation or a larger enclosure may be needed if multiple breakers are ganged.

Frequently asked questions

Where can I buy 3VA2116-5JQ32-0BC0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing; confirmation comes at quote time.

What is the interrupting capacity of 3VA2116-5JQ32-0BC0 at 240 V?

187 kA at 240 VAC, which is the highest interrupting rating on this breaker — it drops to 121 kA at 415 V and 440 V, then 75.6 kA at 500 V, and 3.7 kA at 690 V.

What are the physical dimensions of 3VA2116-5JQ32-0BC0?

Width 105 mm, height 181 mm, depth 86 mm — standard SENTRON MCCB form factor that fits existing panel cutouts and DIN-rail mounting patterns.

Does 3VA2116-5JQ32-0BC0 include an undervoltage release?

Yes, the design includes an undervoltage release (UVR) as the auxiliary release, plus two HQ-rated auxiliary switches for status signaling.

MPN
3VA2116-5JQ32-0BC0