Skip to main content
Siemens 3VA2116-5JQ32-0CA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2116-5JQ32-0CA0 SENTRON MCCB, 160 A, 3-Pole

MPN3VA2116-5JQ32-0CA0

Siemens SENTRON 3VA2116-5JQ32-0CA0, molded case circuit breaker, 160 A, 3-pole, ETU560 electronic trip unit, line protection version, 187 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2116-5JQ32-0CA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2116-5JQ32-0AA0
3VA2116-5JQ32-0CA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C154 A
Current at 60 °C148 A
Current at 65 °C142 A
Current at 70 °C136 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V79 kA
Breaking capacity at 690 V4.25 kA
Power loss, max.28 W
3VA2116-5JQ32-0CA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560
3VA2116-5JQ32-0CA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2116-5JQ32-0CA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2116-5JQ32-0CA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2116-5JQ32-0CA0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

160 A MCCB with ETU560 — the so-what for your panel

At 240 V it interrupts 187 kA; at 415 V and 440 V it holds 121 kA, which covers most industrial distribution panels without needing a current-limiting upstream device. The 105 mm width and 181 mm height are standard 3VA frame dimensions, so it lands on the same mounting footprint as other 3VA breakers in this frame class.

Temperature derating — don't guess, use the curve

Above that it derates linearly: 154 A at 55 °C, 148 A at 60 °C, 142 A at 65 °C, 136 A at 70 °C. The maximum power loss is 28 W, which is modest for a 160 A frame but still needs to be factored into the enclosure thermal budget.

What's built into this variant

It has a communication function on board — useful for remote monitoring or integration into a higher-level energy management system. There is no auxiliary contact block fitted (the auxiliary contact version is listed as "Without"), and no voltage trigger or phase failure detection.

Frequently asked questions

How do I get current pricing and availability for 3VA2116-5JQ32-0CA0?

Submit an RFQ against this order code. The part is sourced through independent distribution channels; availability and current pricing are confirmed at quote time, not on a public listing.

What is the breaking capacity at different voltages?

At 240 V it interrupts 187 kA; at 415 V and 440 V it interrupts 121 kA; at 500 V it interrupts 79 kA; at 690 V it interrupts 4.25 kA. These are the maximum fault currents the breaker can safely clear at each voltage level.

Will 3VA2116-5JQ32-0CA0 drop into a panel specified around 3VA1112-5EF32-0CA0 without rewiring?

Both are 3VA frame breakers, so the mounting footprint and bus-bar connections are the same. The 3VA2116 is a higher-current frame (160 A vs the 3VA1112's lower rating), so the main difference is the trip unit and the continuous current rating — verify your load current and cable sizing against 160 A before swapping.

MPN