Skip to main content
Siemens 3VA2116-5JQ32-0CA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2116-5JQ32-0CA0 SENTRON MCCB, 160 A, 3-Pole

MPN3VA2116-5JQ32-0CA0

Siemens SENTRON 3VA2116-5JQ32-0CA0, molded case circuit breaker, 160 A, 3-pole, ETU560 electronic trip unit, line protection version, 187 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2116-5JQ32-0CA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2116-5JQ32-0AA0

Ratings

3VA2116-5JQ32-0CA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C154 A
Current at 60 °C148 A
Current at 65 °C142 A
Current at 70 °C136 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V79 kA
Breaking capacity at 690 V4.25 kA
Power loss, max.28 W

Protection & Trip Unit

3VA2116-5JQ32-0CA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560

Construction & Connection

3VA2116-5JQ32-0CA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2116-5JQ32-0CA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2116-5JQ32-0CA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2116-5JQ32-0CA0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

160 A MCCB with ETU560 — the so-what for your panel

The Siemens 3VA2116-5JQ32-0CA0 is a 3-pole SENTRON molded case circuit breaker rated for 160 A continuous current, built around the ETU560 electronic trip unit. That trip unit gives you adjustable long-time, short-time, instantaneous, and ground-fault protection curves — meaning you can shape the trip response to match your load, not the other way around. At 240 V it interrupts 187 kA; at 415 V and 440 V it holds 121 kA, which covers most industrial distribution panels without needing a current-limiting upstream device. The 105 mm width and 181 mm height are standard 3VA frame dimensions, so it lands on the same mounting footprint as other 3VA breakers in this frame class.

Temperature derating — don't guess, use the curve

This breaker carries its full 160 A rating from 40 °C through 50 °C. Above that it derates linearly: 154 A at 55 °C, 148 A at 60 °C, 142 A at 65 °C, 136 A at 70 °C. If your panel ambient runs hot — say near a VFD bank or a transformer compartment — size the downstream load against the derated figure for your actual enclosure temperature, not the nameplate. The maximum power loss is 28 W, which is modest for a 160 A frame but still needs to be factored into the enclosure thermal budget.

What's built into this variant

The 3VA2116-5JQ32-0CA0 comes with an integrated undervoltage release (UVR) as the auxiliary release design. It has a communication function on board — useful for remote monitoring or integration into a higher-level energy management system. There is no auxiliary contact block fitted (the auxiliary contact version is listed as "Without"), and no voltage trigger or phase failure detection. The ground-fault monitoring uses summation current formation on the L-conductor. The supplied basic switch is order code 3VA2116-5JQ32-0AA0; the integrated auxiliary trip is 3VA9608-0BB24.

Frequently asked questions

How do I get current pricing and availability for 3VA2116-5JQ32-0CA0?

Submit an RFQ against this order code. The part is sourced through independent distribution channels; availability and current pricing are confirmed at quote time, not on a public listing.

What is the breaking capacity at different voltages?

At 240 V it interrupts 187 kA; at 415 V and 440 V it interrupts 121 kA; at 500 V it interrupts 79 kA; at 690 V it interrupts 4.25 kA. These are the maximum fault currents the breaker can safely clear at each voltage level.

Will 3VA2116-5JQ32-0CA0 drop into a panel specified around 3VA1112-5EF32-0CA0 without rewiring?

Both are 3VA frame breakers, so the mounting footprint and bus-bar connections are the same. The 3VA2116 is a higher-current frame (160 A vs the 3VA1112's lower rating), so the main difference is the trip unit and the continuous current rating — verify your load current and cable sizing against 160 A before swapping.

MPN
3VA2116-5JQ32-0CA0