Skip to main content
Siemens 3VA2116-5JQ32-0DH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2116-5JQ32-0DH0 SENTRON MCCB, 160 A, 3-Pole, 187

MPN3VA2116-5JQ32-0DH0

Siemens SENTRON 3VA2116-5JQ32-0DH0, molded case circuit breaker, 3-pole, 160 A, line protection, 187 kA at 240 V, undervoltage release, 2 aux + 1 trip alarm switch.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2116-5JQ32-0DH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21165JQ320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA2116-5JQ32-0DH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.28 W

Protection & Trip Unit

3VA2116-5JQ32-0DH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560
Overcurrent protection functionLSIG
Ground-fault monitoringSummation current formation L-conductor
Grounding protection functionYes

Construction & Connection

3VA2116-5JQ32-0DH0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2116-5JQ32-0DH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA2116-5JQ32-0DH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2116-5JQ32-0DH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2116-5JQ32-0DH0 is a 3-pole molded case circuit breaker rated 160 A continuous, designed for line protection in distribution panels. Its breaking capacity reaches 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V — so at typical 400 V industrial feeds it handles high fault currents without cascading upstream. The thermal-magnetic trip unit adjusts from 32 A to 160 A full-scale, and the breaker carries a trip indicator for quick fault isolation. Current rating holds flat at 160 A from 40 °C through 70 °C ambient — no derating curve to calculate for warm enclosures. Power loss at full load is 28 W maximum, which is manageable for a 160 A frame in a ventilated panel.

Integration & Mounting

The MCCB measures 105 mm wide, 181 mm high, and 86 mm deep — a standard 3-pole frame that fits common panel cutouts and busbar arrangements. It ships with an undervoltage release (UVR) and a factory-fitted auxiliary switch block: 2 auxiliary switches plus 1 trip alarm switch (HQ type). Communication function is onboard, so it can integrate with energy management or remote monitoring systems without an add-on module.

Environmental & Compliance

Operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C. The SENTRON series carries IEC/UL certifications typical for molded case breakers — compliance documentation (RoHS, REACH, UL, IEC) is provided by Siemens with the unit.

Frequently asked questions

How do I get current pricing and availability for 3VA2116-5JQ32-0DH0?

This part is quoted to order against an RFQ. Availability and current pricing are confirmed at quote time through our independent distribution network.

What is the breaking capacity of 3VA2116-5JQ32-0DH0 at 415 V?

121 kA at 415 V, same as at 440 V. At 240 V it reaches 187 kA, at 500 V it is 75.6 kA, and at 690 V it is 3.7 kA.

What auxiliary switches come with 3VA2116-5JQ32-0DH0?

It includes 2 auxiliary switches plus 1 trip alarm switch (HQ design). An undervoltage release is also fitted.

Does 3VA2116-5JQ32-0DH0 require derating at high ambient temperatures?

No — the 160 A rating holds flat from 40 °C through 70 °C ambient. No derating calculation needed for warm enclosures.

MPN
3VA2116-5JQ32-0DH0