Skip to main content
Siemens 3VA2116-5JQ32-0JH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2116-5JQ32-0JH0 SENTRON MCCB, 160 A, 3-Pole, 187

MPN3VA2116-5JQ32-0JH0

Siemens SENTRON 3VA2116-5JQ32-0JH0, 3-pole molded case circuit breaker, 160 A continuous, 187 kA interrupting at 240 V, line protection design, with communication function and shunt trip.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2116-5JQ32-0JH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21165JQ320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA2116-5JQ32-0JH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.25.5 W

Protection & Trip Unit

3VA2116-5JQ32-0JH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560
Overcurrent protection functionLSIG
Ground-fault monitoringSummation current formation L-conductor
Grounding protection functionYes

Construction & Connection

3VA2116-5JQ32-0JH0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2116-5JQ32-0JH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA2116-5JQ32-0JH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2116-5JQ32-0JH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this MCCB carries — and where it fits

The Siemens 3VA2116-5JQ32-0JH0 is a SENTRON molded case circuit breaker rated for 160 A continuous at 40 °C, with a 3-pole line-protection design. Its interrupting capacity reaches 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V — so the SCCR headroom drops fast above 500 V; at 690 V the breaker is still rated but the available fault current must stay under 3.7 kA. The continuous rating holds flat at 160 A from 40 °C through 70 °C, which simplifies derating in warm enclosures — no need to recalculate for a panel that runs at 55 °C. It ships with a built-in communication function and includes a basic switch (order code 3VA21165JQ320AA0), plus two auxiliary switches and one trip-alarm switch (HQ) plus a shunt trip release (STL). That means the breaker can report its status to a PLC or BMS without an external interface module.

Panel fit and integration

Dimensions are 181 mm high, 105 mm wide, 86 mm deep — a standard SENTRON 3VA footprint for 160 A frame. It mounts on a DIN rail or panel-mount adapter; the 3-pole body leaves room for side-mounted auxiliary switches without crowding adjacent breakers in a multi-unit lineup. Power loss is 25.5 W maximum — relevant for thermal budgeting inside a sealed enclosure; at 160 A load the dissipation is manageable but should be factored into the cabinet cooling calculation.

Frequently asked questions

Where can I buy 3VA2116-5JQ32-0JH0 and what is the lead time?

We source this breaker to order against an RFQ. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead-time and price.

What is the interrupting capacity at 415 V?

At 415 V the breaker is rated for 121 kA interrupting capacity. The same rating applies at 440 V.

Does this MCCB include auxiliary switches or a shunt trip?

Yes — it comes with two auxiliary switches, one trip-alarm switch (HQ), and a shunt trip release (STL). Communication function is also built in.

What compliance documentation does Siemens provide for this breaker?

The SENTRON 3VA series carries UL, IEC, and CSA certifications; RoHS and REACH declarations are available from Siemens. Specific document numbers are confirmed at quote time.

MPN
3VA2116-5JQ32-0JH0