The Siemens SENTRON 3VA2116-5JQ36-0AK0 is a 3-pole molded case circuit breaker (MCCB) with an adjustable thermal-magnetic trip unit covering 32 A to 256 A, factory-set at 160 A. Breaking capacity at 415 V is 121 kA, which covers most industrial fault levels upstream of a transformer or generator. At 240 V it rises to 187 kA; at 690 V it drops to 3.7 kA — the part is sized for low-voltage distribution, not 690 V motor circuits. It ships with one auxiliary switch, one trip alarm switch, and one electrical alarm switch (HQ type), plus a communication function for remote status or integration into a BMS or PLC. No undervoltage release is fitted on this variant.
The 86 mm depth leaves clearance for rear-connected busbars in a typical distribution cabinet.