It is rated for 160 A continuous current and carries a 4-pole configuration, meaning it switches and protects all four conductors — three phases plus neutral — in a three-phase system. The key selection figure is the interrupting capacity: 187 kA at 240 V, 121 kA at 415 V/440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V. It includes a communication function and summation-current ground-fault monitoring on the L+N conductors, so it can report status and detect ground leaks without a separate module.
That simplifies panel sizing: no thermal correction factor needed up to 70 °C ambient. Maximum power loss is 25.5 W — relevant for ventilation planning in a sealed enclosure.
Integration notes
The 86 mm depth fits standard enclosures with clearance for rear-connected busbars. The communication function allows integration with a higher-level control system for remote trip indication and load monitoring — no separate aux contact block required for basic status.