This MCCB delivers 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V. The steep drop at 690 V means it is not a primary choice for 690 V line-side protection unless fault current is tightly bounded; at standard 400/415 V distribution levels the 121 kA rating handles most industrial service-entrance and feeder applications.
Thermal performance and panel integration
Maximum power loss is 28 W, manageable for enclosed panel thermal budgets.