Skip to main content
Siemens 3VA2116-5KP36-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2116-5KP36-0AA0 SENTRON MCCB, 160 A, ETU850, 3-Po

MPN3VA2116-5KP36-0AA0
Active

Siemens SENTRON 3VA2116-5KP36-0AA0, molded case circuit breaker, 3-pole, 160 A, ETU850 electronic overcurrent release, line protection design, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2116-5KP36-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2116-5KP36-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.25.5 W
3VA2116-5KP36-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2116-5KP36-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2116-5KP36-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts0
3VA2116-5KP36-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2116-5KP36-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

160 A MCCB with ETU850 — line protection for distribution panels

It's designed for line protection in main or feeder distribution panels, not motor branch circuits — the ETU850 gives you adjustable long-time, short-time, instantaneous, and ground-fault protection curves, which is what you need for selective coordination downstream. Breaking capacity is the headline here: 187 kA at 240 V, 121 kA at 415/440 V, 75.6 kA at 500 V, and still 3.7 kA at 690 V.

Communication function is built in, so you can integrate it with a BMS or SCADA system for remote monitoring and trip-event logging — no separate module required for basic connectivity. The ETU850 supports this natively.

Frequently asked questions

What is the breaking capacity of 3VA2116-5KP36-0AA0 at 415 V?

121 kA at 415 V, and the same at 440 V. At 240 V it reaches 187 kA; at 500 V it's 75.6 kA; at 690 V it's 3.7 kA.

What trip unit does this MCCB use?

The ETU850 electronic overcurrent release, which provides adjustable LSI (long-time, short-time, instantaneous) protection and supports ground-fault monitoring when the appropriate module is added.

Where can I buy 3VA2116-5KP36-0AA0?

We source it to order through independent distribution. Submit an RFQ for current availability and pricing — lead time is confirmed at quote time.

MPN
3VA2116-5KP36-0AA0