Skip to main content
Siemens 3VA2116-6HL32-0AB0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2116-6HL32-0AB0 SENTRON MCCB, 160 A, 3-pole, 242

MPN3VA2116-6HL32-0AB0

Siemens SENTRON 3VA2116-6HL32-0AB0, molded case circuit breaker, 3-pole, 160 A, line protection, breaking capacity 242 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2116-6HL32-0AB0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21166HL320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA11

Ratings

3VA2116-6HL32-0AB0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.25.5 W

Protection & Trip Unit

3VA2116-6HL32-0AB0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2116-6HL32-0AB0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2116-6HL32-0AB0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2116-6HL32-0AB0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2116-6HL32-0AB0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

160 A MCCB for line protection — flat derating to 70 °C

The Siemens SENTRON 3VA2116-6HL32-0AB0 is a 3-pole molded case circuit breaker rated for 160 A continuous current, designed specifically for line protection — meaning it guards the feeder or distribution bus against overloads and short circuits, not a specific motor or load branch. Its continuous current rating holds flat at 160 A from 40 °C all the way up to 70 °C ambient, so no derating is needed in a warm enclosure — a practical advantage when the breaker sits near other heat sources on the DIN rail. Breaking capacity ranges from 242 kA at 240 V down to 3.7 kA at 690 V; at the common 415 V and 440 V levels it delivers 187 kA, which covers most industrial distribution panels with high fault current. Maximum power loss is 25.5 W, which factors into enclosure thermal budgeting when grouping multiple breakers.

Footprint and panel integration

Dimensions are 86 mm deep, 105 mm wide, and 181 mm tall — a standard 3-pole MCCB footprint that fits existing SENTRON mounting bases and busbar systems without panel rework. Operating temperature range is -25 °C to 70 °C; storage range extends from -40 °C to 80 °C, so the breaker handles cold warehouse storage and warm panel operation without issue.

Frequently asked questions

Will 3VA2116-6HL32-0AB0 drop into a panel specified around 3VA2116-5HL32-0AK0?

Both are 3-pole SENTRON MCCBs with the same 160 A continuous rating and identical 86 x 105 x 181 mm footprint, so mechanical fit and busbar connection are the same — no rewiring needed for the panel layout.

What is the depth of 3VA2116-6HL32-0AB0?

The depth is 86 mm (3.39 in), which matches the standard SENTRON 3VA2 MCCB depth.

MPN
3VA2116-6HL32-0AB0