Skip to main content
Siemens 3VA2116-6HL32-0CH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2116-6HL32-0CH0 SENTRON MCCB, 160 A, 3-Pole, 242

MPN3VA2116-6HL32-0CH0

Siemens SENTRON 3VA2116-6HL32-0CH0, molded case circuit breaker, 3-pole, 160 A, line protection, undervoltage release, 2 aux + 1 trip alarm switch, 86 x 105 x 181 mm.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2116-6HL32-0CH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA21166HL320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA2116-6HL32-0CH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C160 A
Current at 60 °C160 A
Current at 65 °C160 A
Current at 70 °C160 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.28 W

Protection & Trip Unit

3VA2116-6HL32-0CH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2116-6HL32-0CH0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2116-6HL32-0CH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA2116-6HL32-0CH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2116-6HL32-0CH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

Siemens SENTRON 3VA2116-6HL32-0CH0 — 160 A MCCB with Undervoltage Release

The Siemens SENTRON 3VA2116-6HL32-0CH0 is a 3-pole molded case circuit breaker (MCCB) rated for 160 A continuous current, designed for line protection in distribution panels and industrial switchboards. It carries a breaking capacity of 242 kA at 240 V AC, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3.7 kA at 690 V — so the interrupting rating you need to match against the available fault current at the installation point varies significantly with system voltage.

Key Ratings and What They Mean for Fit

The 160 A continuous rating holds across the full ambient temperature range from -25 °C to 70 °C — no derating curve to chase for standard panel environments. The 3-pole construction suits three-phase line protection; the unit is not fitted with ground-fault monitoring or communication functions, so it is a straightforward thermal-magnetic or electronic trip MCCB for feeder protection. Maximum power loss is 28 W at rated current — a figure to check against enclosure thermal rise if the panel is densely packed. Dimensions are 86 mm deep, 105 mm wide, 181 mm high, fitting standard MCCB mounting footprints in switchboards. The unit ships with an undervoltage release (UVR) and a 2-auxiliary-switch plus 1-trip-alarm-switch configuration — the UVR means the breaker trips if control voltage drops below the dropout threshold, which is typical for emergency-stop or undervoltage protection schemes. The auxiliary contacts provide status feedback for PLC or indication circuits.

Panel Integration and Deployment Context

As a SENTRON MCCB, it mounts into standard switchboard or panelboard cutouts with screw-clamp or plug-in connections depending on the base. The 105 mm width and 86 mm depth fit typical MCCB slots in distribution panels; verify the busbar or cable connection method against the panel's existing design.

Frequently asked questions

Where can I buy 3VA2116-6HL32-0CH0 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at the time of quote — submit an RFQ for a firm price and lead time.

What is the breaking capacity of 3VA2116-6HL32-0CH0 at different voltages?

Breaking capacity is 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3.7 kA at 690 V. The interrupting rating drops significantly above 500 V, so verify the available fault current at your system voltage.

What auxiliary switches and releases are included with this MCCB?

It includes an undervoltage release (UVR) and a configuration of 2 auxiliary switches plus 1 trip alarm switch (HQ type). The UVR trips the breaker on loss of control voltage; the auxiliary switches provide status feedback.

MPN
3VA2116-6HL32-0CH0